Instruction Manual
Instruction Manual
D103216X012
L2sj Controller
January 2015
8
Figure 4. Setup and Adjustments Label (Inside Fisher L2sj Cover)
GE16844
1. Set the supply pressure to 25 psig.
Note
Supply pressure can be set between 0.34 and 2.4 bar (5 and 35 psig).
2. Set the span adjuster to the maximum sensitivity.
3. Turn the spring adjustor to tighten the spring to it's maximum extension. If the output pressure rises, loosen the