Data Sheet

i2P-100 Transducer
D103197X012
Product Bulletin
62.1:i2P-100
July 2014
3
Specifications
Input Signal
Available as standard with 4-20 mA.
User configurable by dip switch for split ranging, see
table below.
Output Signal
Available as standard 0.2 to 1.0 bar (3 to 15 psig),
0.4 to 2.0 bar (6 to 30 psig), or 0.14 to 2.3 bar
(2 to 33 psig). User configurable by dip switch
selection and zero and span potentiometer
adjustment, see table below.
INPUT SIGNAL
OUTPUT PRESSURE
Bar Psig
4 to 20 mA DC
0.2 to 1.0 3 to 15
0.4 to 2.0 6 to 30
0.14 to 2.3 2 to 33
4 to 12 mA DC 0.2 to 1.0 3 to 15
12 to 20 mA DC 0.2 to 1.0 3 to 15
Equivalent Circuit
The i2P-100 equivalent circuit is a series circuit
consisting of a constant voltage drop (battery) of
approximately 4 VDC and a total resistance of 40
ohms. Input is shunted by two 6.8 V zener diodes (see
figure 4).
Supply Pressure
(1)
Recommended: 0.34 bar (5 psi) higher than upper
range limit of output signal
Maximum: 3.4 bar (50 psig)
Medium: Air or Natural Gas
Maximum Steady-State Flow Rate
(2)(3)
Refer to tables 2 and 3
Maximum Output Air Capacity
(3)
8.04 m
3
/hr (300 scfh) at 1.4 bar (20 psig) supply
pressure
Performance
(4)
Reference Accuracy: ±1.0% of full scale output span;
includes combined effects of hysteresis, linearity, and
deadband
Independent Linearity: ±0.5% of full scale output span
Hysteresis: 0.4% of full scale output span
Frequency Response: Gain is attenuated 3 dB at 3 Hz
with transducer output signal piped to a typical
instrument input
Temperature Effect: $0.14% per degrees Celsius
($0.075 per degrees Fahrenheit) of span
Supply Pressure Effect: 0.2% of full scale output span
per psi supply pressure change)
Vibration Effect: Less than 1% of full scale output span
when tested to ISA S75.13
Electromagnetic Compatibility
Meets EN 61326-1 (First Edition)
Immunity—Industrial locations per Table 2 of
EN 61326-1 Standard. Performance is
shown in table 1 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Operating Ambient Temperature Limits
(1)
-40 to 85_C (-40 to +185_F)
Electrical Seal
Single sealed device per ANSI/ISA 12.27.01
Electrical Classification
Hazardous Area:
CSA — Intrinsically Safe, Explosion proof,
Type n, Dust‐Ignition proof
FM— Intrinsically Safe, Explosion proof,
Type n, Non‐incendive, Dust‐Ignition proof
ATEX— Intrinsically Safe, Flameproof , Type n
IECEx— Intrinsically Safe, Flameproof, Type n
Refer to tables 4, 5, 6, and 7 for specific approval
information.
Electrical Housing:
When Remotely Vented No Remote Venting
CSA—Type 4X Encl.
FM— NEMA 4X
ATEX—IP66
IECEx—IP66
CSA—Type 3 Encl.
FM— NEMA 3
ATEX—IP64
IECEx—IP64