Instruction Manual
Instruction Manual
D103198X012
i2P-100 Transducer
July 2014
21
3. Electrically calibrate the unit using the procedure in the Calibration section of this manual.
4. Replace the housing cap (key 2), making sure to re‐tighten the set screw (key 8).
Relay Maintenance
Refer to figures 12 and 14 for key number locations.
Figure 12. Valve Plug, Inner Valve Spring and Body Plug Assembly
VALVE PLUG
(KEY 39)
ONE OF THREE
TABS ON VALVE
PLUG
END OF SPRING COIL
BODY PLUG
(KEY 32)
O‐RING
(KEY 42)
INNER VALVE
SPRING (KEY 35)
A6057‐1
Removal
1. Remove the four mounting screws (key 36, shown in figure 14) and remove the relay from the transducer. Be
careful not to lose the bias spring (key 34) and input diaphragm (key 38).
2. Remove the body plug (key 32) that holds the inner valve spring (key 35) and valve plug (key 39) in place from the
relay body assembly.
3. Remove the exhaust port assembly (key 33) from the relay assembly.
4. Inspect the springs, exhaust seat, valve plug, and other parts for wear or damage; replace as necessary. Note: the
valve plug supply seat is an insert in the relay body (key 41). If this insert is bad, replace the relay body.
5. Make sure all parts of the relay are clean and that all passages are clear of foreign matter.
Assembly
Note
The relay will not function properly if the tabs on the body block and the relay body are not aligned as specified with the transducer
housing assembly in the following procedure.