Instruction Manual

Instruction Manual
D103198X012
i2P-100 Transducer
July 2014
15
WARNING
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous location, ingress protection,
and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage
from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval.
Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or
explosion.
Use the 1/2 NPT conduit connection, shown in figure 5, for installation of field wiring.
Refer to figures 8, 9, and 10 when connecting field wiring from the control device to the transducer. Connect the
positive wire from the control device to the transducer “+” terminal and, the negative wire from the control device to
the transducer “-” terminal. Do not overtighten the terminal screws. Maximum torque is 0.45 NSm (4 lbfSin.). Connect
the transducer grounding terminal to earth ground.
Grounding terminals are provided both inside and outside the transducer housing.
Figure 8. Typical Field Wiring Diagram
+
+
+
1
CONTROL
DEVICE
TRANSDUCER
HOUSING
TERMINAL
BLOCK
FIELD WIRING
EARTH
GROUND
NOTE:
 FOR TROUBLESHOOTING OR MONITORING OPERATION,
AN INDICATING DEVICE CAN BE A VOLTMETER ACROSS
A 250 OHM RESISTOR OR A CURRENT METER.
1
A3875
Figure 9. Equivalent Circuit
4 - 20 mA
6.8V 6.8V 4V
40 Ohm
Operating Information
During normal operation, the output of the i2P‐100 transducer is connected to the final control element.
Calibration
WARNING
On explosion‐proof instruments, or when using natural gas as the supply medium, remove electrical power before
removing either of the housing caps in a hazardous area. Personal injury or property damage may result from fire or
explosion if power is applied to the transducer with the cap removed in a hazardous area.