Quick Start Guide

Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
January 2014
66
1 SEE NOTES IN FIGURE 60
IECEx
APPROVED
ENTITY
DEVICE
HAZARDOUS LOCATION
NON‐HAZARDOUS LOCATION
ZONE 0, Ex ia IIC
Ui = 30 VDC
Ii = 226 mA
Ci = 50 nF
Li = 0.55 mH
Pi = 1.4 W
IECEx APPROVED
BARRIER
NON‐HAZARDOUS LOCATION
HAZARDOUS LOCATION
ENTITY FIELDBUS LOOP
IECEx APPROVED
FISCO BARRIER
IECEx APPROVED
FISCO TERMINATOR
IECEx
APPROVED
FISCO DEVICE
FISCO LOOP
1 NOTE 1, 3, 4
NOTE 1, 3 1
NOTE 5 1
1 NOTE 2, 3, 4
NOTE 2, 3 1
GE42990 Sheet 10, Rev. C
T CODE T (amb)
Figure 59. IECEx Loop Schematics FIELDVUE DVC6205f, DVC6205p, and DVC6215
NOTE 1 1
DVC6205f, DVC6205p
Uo = 24 VDC
Io = 44 mA
Ca = 121 nF
La = 30 mH
Po = 0.33 W
Ui = 24 VDC
Ii = 380 mA
Ci = 5 nF
Li = 0 mH
Pi = 1.4 W
DVC6215
Ui = 30 VDC
Ii = 226 mA
Ci = 50 nF
Li = 0.55 mH
Pi = 1.4 W
Ui = 17.5 VDC
Ii = 380 mA
Ci = 5 nF
Li = 0 mH
Pi = 5.32 W
DVC6215
ZONE 0, Ex ia IIC
DVC6205f, DVC6205p
Uo = 17.5 VDC
Io = 44 mA
Ca = 121 nF
La = 30 mH
Po = 0.33 W
NOTE 2 1
ZONE 0, Ex ia IIC
ZONE 0, Ex ia IIC
T CODE T (amb)
T CODE T (amb)
T CODE T (amb)
T4 80_C
T5 77_C
T6 62_C
T4 80_C
T5 77_C
T6 62_C
T4 125_C
T5 90_C
T6 75_C
T4 125_C
T5 90_C
T6 75_C
GE42990 Sheet 9, Rev. C