Quick Start Guide

Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
January 2014
62
Intrinsically Safe
WARNING
Potential electrostatic charging hazard. See warning on page 2.
Ex ia IIC
IP66
Intrinsically safe when connected per drawing GE42990, as shown in the following figures
DVC6200 HW1 figure 55 and 60...........................................
DVC6200 HW2 and DVC6200 SIS figure 56 and 60...........................
DVC6205, DVC6205 SIS, and DVC6215 Remote Mount figure 57 and 60........
DVC6200f and DVC6200p figure 58 and 60..................................
DVC6205f, DVC6205p, and DVC6215 Remote Mount figure 59 and 60..........
GE42990 Sheet 2, Rev. E
IECEx APPROVED BARRIER
1 NOTE 1, 3, 4
1 NOTE 5
NON‐HAZARDOUS LOCATION
ZONE 0, Ex ia IIC
Vmax = 30 VDC
Imax = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
HAZARDOUS LOCATION
Figure 55. IECEx Schematic—FIELDVUE DVC6200 HW1
1 SEE NOTES IN FIGURE 60
T CODE T (amb)
T5 80_C
T6 75_C
DVC6200, DVC6200S