Quick Start Guide

Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
January 2014
11
Fisher Rotary Actuators
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lock‐out procedures to
be sure that the above measures stay in effect while working on the equipment.
Figure 10. Mounting on Rotary Actuators
ROTARY MOUNTING KIT
(DVC6200 NOT SHOWN)
W9708
2. Verify that the appropriate cam is installed on the actuator as described in the instructions included with the
mounting kit.
Figure 11. Rotary Actuator Mounting Variations
E1229
NOTE THE DIFFERENCE IN THE SHAPE AND LENGTH OF THE ROLLER ARM
ROLLER ARM
2052 SIZE 2 AND 3
1051/1052 SIZE 40-70
SIZE 1061 SIZE 30-100
ROLLER ARM
ROLLER ARM
2052 SIZE 1
1051 SIZE 33
1052 SIZE 20-33
3. Mount the DVC6200 on the actuator as follows:
D If required, a mounting adaptor is included in the mounting kit. Attach the adaptor to the digital valve controller,
then attach the digital valve controller assembly to the actuator. The roller on the digital valve controller
feedback arm will contact the actuator cam as it is being attached.
D If no mounting adaptor is required, attach the digital valve controller and mounting kit assembly to the actuator.
The roller on the digital valve controller feedback arm will contact the actuator cam as it is being attached.
4. For remote mount applications, proceed to page 13 for DVC6205 base unit mounting. Otherwise, proceed to
Step 2—Connect the Pneumatic Tubing on page 15.