8. Using a 5 mm hex wrench, attach the digital valve controller to the GX actuator mounting pad.
9. Check for clearance between the magnet assembly and the DVC6200 feedback slot.
10. Install tubing between the actuator casing and the appropriate DVC6200 pneumatic output port.
11. If not already installed, install a vent in the port on the lower diaphragm casing.
12. For remote mount applications, proceed to page 13 for DVC6205 base unit mounting. Otherwise, proceed to
Step 2—Connect the Pneumatic Tubing on page 15.
Note
When field converting a GX actuator from air-to-close to air-to-open (or vice‐versa), you will need to change the plugs for the
pneumatic passages in the DVC6200 housing.
D
To convert to air-to-open, remove the R1/8 pneumatic plug on the back of the DVC6200 housing and install an O‐ring. Plug
the external pneumatic output with a 1/4 NPT plug. Refer to figure 8.
D
To convert to air-to-close, remove the external pneumatic plug. Install an R1/8 plug on the back of the DVC6200 housing.
Install tubing between the pneumatic output connection of the DVC6200 to the pneumatic port on top of the actuator
casing.