Brochure

14 | A Single Instrument Solution
KEY SPECIFICATIONS.
Specification
DVC6200
HART
DVC6200f and DVC6200p
Foundation fieldbus and PROFIBUS
Input
Analog input signal: 4−20 mA DC, nominal;
split ranging available.
Minimum voltage available at instrument
terminals must be 10.5 VDC for analog control,
11 VDC for HART communication.
Voltage Level: 9 to 32 volts.
Maximum Current: 19 mA.
Reverse Polarity Protection: Unit is not polarity
sensitive.
Termination: Bus must be properly terminated per
ISA SP50 guidelines.
Electrical
Classification
Hazardous Area Approvals:
n
CSA: Intrinsically Safe, Explosion-proof,
Division 2, Dust Ignition−proof
n
FM: Intrinsically Safe, Explosion-proof,
Non−Incendive, Dust Ignition-proof
n
ATEX: Intrinsically Safe, Flameproof, Type n
n
IECEx: Intrinsically Safe, Flameproof, Type n
Electrical Housing:
n
CSA: Type 4X, IP66
n
FM: Type 4X, IP66
n
ATEX: IP66
n
IECEx: IP66
Other certifications are available. Contact your
Emerson sales office for specific classification/
certification information.
Hazardous Area Approvals:
n
CSA: Intrinsically Safe, FISCO, Explosion-proof,
Division 2, Dust Ignition−proof
n
FM: Intrinsically Safe, FISCO, Explosion-proof,
Non−Incendive, Dust Ignition−proof
n
ATEX: Intrinsically Safe, FISCO, Flameproof, Type n
n
IECEx: Intrinsically Safe, FISCO, Flameproof, Type n
Electrical Housing:
n
CSA: Type 4X, IP66
n
FM: Type 4X, IP66
n
ATEX: IP66
n
IECEx: IP66
Other certifications are available. Contact your
Emerson sales office for specific classification/
certification information.
Supply Pressure Maximum: 10.0 bar (145 psig) or maximum pressure rating of the actuator, whichever is lower
Temperature Limits
-40 to 85°C (-40 to 185°F)
-52 to 85°C (-62 to 185°F) with extreme temperature option
-52 to 125°C (-62 to 257°F) with remote mount option
Available Mounting
n
Sliding-stem linear applications
n
Rotary shaft applications
n
Integral mounting to Fisher rotary actuators
n
Integral mounting to the Fisher GX control valve and actuator system
n
IEC 60534-6-1, IEC 60534-6-2, VDI/VDE 3845, and NAMUR standards
n
Remote mount
Options
n
Extreme temperature
n
Remote mount
n
Stainless steel
n
Low-bleed relay
n
Integral 4-20mA position transmitter
1
n
Integral switch
1
n
Natural gas certified, single seal device
n
Constructions to meet US Environmental
Protection Agency emissions requirements
2
1
The electronic output is configurable as either the position transmitter or
the switch
2
New Source Performance Standards Subpart OOOO, EPA-HQ-QAR-2010-0505
n
Extreme temperature
n
Remote mount
n
Stainless steel
n
Low-bleed relay
n
Natural gas certified, single seal device
n
Constructions to meet US Environmental
Protection Agency emissions requirements
2
2
New Source Performance Standards Subpart OOOO, EPA-HQ-QAR-2010-0505
System Integration
Technology
eDDL, FDT/DTM, AMS Device Manager SNAP-ON, PRM Plug-In
Instrument
Certification
HART Communication Foundation
HART 5 and 7
Fieldbus Foundation
PROFIBUS International