Data Sheet

DVC6200p Digital Valve Controller
D103564X012
Product Bulletin
62.1:DVC6200p
September 2013
3
Specifications
Available Mounting
J Integral mounting to the Fisher GX Control
  Valve and Actuator System
J Integral mounting to Fisher rotary actuators,
J Sliding‐stem linear applications
J Quarter‐turn rotary applications
DVC6200p digital valve controllers can also be mounted on
other actuators that comply with IEC 60534‐6‐1,
IEC 60534‐6‐2, VDI/VDE 3845 and NAMUR mounting
standards.
Function Block Execution Times
AO Block: 6 ms
AI Block: 6 ms
DO Block: 6 ms
DI Block: 6 ms
Electrical Input
Voltage Level: 9 to 32 volts
Maximum Current: 19 mA
Reverse Polarity Protection: Unit is not polarity sensitive
Termination: Bus must be properly terminated per ISA
SP50 guidelines
Digital Communication Protocol
PROFIBUS registered device
Certified to PROFIBUS Profile 3.02
Physical Layer Type(s):
121—Low‐power signaling, bus‐powered, Entity Model I.S.
511—Low‐power signaling, bus‐powered, FISCO I.S.
Supply Pressure
(1)
Minimum Recommended: 0.3 bar (5 psig) higher than
maximum actuator requirements
Maximum: 10.0 bar (145 psig) or maximum pressure rating
of the actuator, whichever is lower
Supply Medium
Air or Natural Gas
Air: Supply pressure must be clean, dry air that meets the
requirements of ISA Standard 7.0.01.
Natural Gas: Natural gas must be clean, dry, oil‐free, and
noncorrosive. H
2
S content should not exceed 20 ppm.
A maximum 40 micrometer particle size in the air system is
acceptable. Further filtration down to 5 micrometer
particle size is recommended.
Output Signal
Pneumatic signal, up to full supply pressure
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action:
J Double, J Single Direct or J Reverse
Steady-State Air Consumption
(2)(3)
At 1.4 bar (20 psig) supply pressure: Less than
0.38 normal m
3
/hr (14 scfh)
At 5.5 bar (80 psig) supply pressure: Less than
1.3 normal m
3
/hr (49 scfh)
Maximum Output Capacity
(2)(3)
At 1.4 bar (20 psig) supply pressure: 10.0 normal m
3
/hr
(375 scfh)
At 5.5 bar (80 psig) supply pressure: 29.5 normal m
3
/hr
(1100 scfh)
Operating Ambient Temperature Limits
(1)(4)
-40 to 85_C (-40 to 185_F)
-52 to 85_C (-62 to 185_F) for instruments utilizing the
Extreme Temperature option (fluorosilicone elastomers)
Independent Linearity
(5)
Typical Value: ±0.50% of output span
Electromagnetic Compatibility
Meets EN 61326-1 (First Edition)
Immunity—Industrial locations per Table 2 of the
EN 61326‐1 standard.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Vibration Testing Method
Tested per ANSI/ISA‐S75.13.01 Section 5.3.5.
Humidity Testing Method
Tested per IEC 61514‐2
-continued-