Quick Start Guide

Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
January 2014
8
Figure 7. Air‐to‐Open Fisher GX Magnet Assembly Alignment
W9218
ALIGNMENT TEMPLATE
INDEX
MARK
FEEDBACK PIECES
VALVE STEM
CONNECTOR
RETAINING
SLOT
7. Tighten the fasteners and remove the alignment template.
Note
Use a flat end hex key to tighten the mounting assembly fasteners to a torque of 2.37 Nm (21 lbfin) for 4 mm screws, and
5.08 Nm (45 lbfin) for 5 mm screws. While tightening the fasteners using the hex key should be sufficient, blue (medium) thread
locker may be used for additional security.
8. Remove the plug (R1/8) from the back of the DVC6200 housing. This pneumatic output port on the DVC6200 lines
up with the integral GX actuator pneumatic port. See figure 8.
Figure 8. Modifications for Fisher GX Actuator; Air‐to‐Open Construction Only
INSTALL O‐RING
INSTALL
1/4 NPT PLUG
REMOVE R1/8 PLUG
W9707