Quick Start Guide

Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
January 2014
65
1 SEE NOTES IN FIGURE 60
IECEx
APPROVED
ENTITY DEVICE
HAZARDOUS LOCATION
NON‐HAZARDOUS LOCATION
ZONE 0, Ex ia IIC
Ui = 24 VDC
Ii = 380 mA
Ci = 5 nF
Li = 0 mH
Pi = 1.4 W
IECEx APPROVED
BARRIER
NON‐HAZARDOUS LOCATION
HAZARDOUS LOCATION
ENTITY FIELDBUS LOOP
IECEx APPROVED
FISCO BARRIER
IECEx APPROVED
FISCO TERMINATOR
IECEx
APPROVED
FISCO DEVICE
DVC6200F, DVC6200FS
DVC6200P, DVC6200PS
FISCO LOOP
1 NOTE 1, 3, 4
NOTE 1, 3 1
1 NOTE 5
1 NOTE 2, 3, 4
NOTE 2, 3 1
GE42990 Sheet 4, Rev. E
ZONE 0, Ex ia IIC
T CODE T (amb)
T4 80_C
T5 77_C
T6 62_C
Figure 58. IECEx Loop Schematics—FIELDVUE DVC6200f and DVC6200p
T CODE T (amb)
T4 80_C
T5 77_C
T6 62_C
GE42990 Sheet 3, Rev. E
DVC6200F, DVC6200FS
DVC6200P, DVC6200PS
Ui = 17.5 VDC
Ii = 380 mA
Ci = 5 nF
Li = 0 mH
Pi = 5.32 W