Quick Start Guide

Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
January 2014
63
1 SEE NOTES IN FIGURE 60
GE42990 Sheet 11, Rev. B
ZONE 0, Ex ia IIC
LOOP TERMINALS
Vmax = 30 VDC
Imax = 130 mA
Ci = 15 nF
Li = 0.55 mH
Pi = 1.0 W
HAZARDOUS LOCATION
POWER MAY BE APPLIED TO
EITHER THE LOOP TERMINALS
OR OUTPUT TERMINALS OR TO
BOTH SETS OF TERMINALS AT
THE SAME TIME
UNITS WITHOUT THE I/O
PACKAGE WILL NOT HAVE
“OUTPUT TERMINALS”
AVAILABLE FOR CONNECTION
1 NOTE 5
Figure 56. IECEx Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS
T5 80_C 80_C
NON‐HAZARDOUS LOCATION
IECEx APPROVED BARRIER
HW2 - WITH OR WITHOUT I/O PACKAGE
DVC6200, DVC6200S
NOTE 1, 3, 4 1
IECEx APPROVED BARRIER
NOTE 1, 3, 4 1
OUTPUT TERMINALS
Vmax = 28 VDC
Imax = 100 mA
Ci = 15 nF
Li = 0.5 mH
Pi = 1.0 W
WITHOUT
I/O PACKAGE
WITH
I/O PACKAGE
T CODE T (amb) T(amb)
T6 61_C 74_C