Quick Start Guide DVC6200 Digital Valve Controllers D103556X012 January 2014 Fisherr FIELDVUE™ DVC6200 Series Digital Valve Controllers Contents Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Step 1. Install the DVC6200 on the Valve . . . . . . . . . . . . . . . . . . . 3 Step 2. Connect the Pneumatic Tubing . . . . . . . . . . . . . . . . . . . 15 Step 3. Connect the Electrical Wires . . . . . . . . . . . . . . . . . . . . . . 19 Step 4.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 SIS Before You Begin Do not install, operate, or maintain a DVC6200 digital valve controller without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is important to carefully read, understand, and follow all contents of this quick start guide, including all safety cautions and warnings.
Quick Start Guide DVC6200 Digital Valve Controllers D103556X012 January 2014 SIS Step 1—Install the DVC6200 on the Valve If ordered as part of a control valve assembly, the factory will mount the digital valve controller on the actuator and calibrate the instrument. If you purchased the digital valve controller separately, you will need a mounting kit. The following procedures are general guidelines.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Sliding‐Stem Linear Actuators Up to 210 mm (8.25 inches) Travel 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment. Figure 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 D For air‐to‐close actuators (e.g. Fisher 657) vertically align the magnet assembly so that the center line of the alignment template is lined up as close as possible with the lower extreme of the valid travel range on the magnet assembly. The magnet assembly should be positioned so that the index mark in the feedback slot of the DVC6200 housing is within the valid range on the magnet assembly throughout the range of travel.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Sliding‐Stem Linear Actuators Over 210 mm (8.25 inches) Travel 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while working on the equipment. Figure 4.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Fisher GX Actuators 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment. 2.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 7. Air‐to‐Open Fisher GX Magnet Assembly Alignment ALIGNMENT TEMPLATE RETAINING SLOT INDEX MARK W9218 FEEDBACK PIECES VALVE STEM CONNECTOR 7. Tighten the fasteners and remove the alignment template. Note Use a flat end hex key to tighten the mounting assembly fasteners to a torque of 2.37 N•m (21 lbf•in) for 4 mm screws, and 5.08 N•m (45 lbf•in) for 5 mm screws.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 9. Install the plug (1/4 NPT, included in the mounting kit) to the external output pneumatic port A. 10. Using a 5 mm hex wrench, attach the digital valve controller to the GX actuator mounting pad on the side that has the open pneumatic port. Be sure to place the O‐ring between the digital valve controller's pneumatic output and the actuator mounting pad.
DVC6200 Digital Valve Controllers January 2014 Quick Start Guide D103556X012 8. Using a 5 mm hex wrench, attach the digital valve controller to the GX actuator mounting pad. 9. 10. 11. 12. Check for clearance between the magnet assembly and the DVC6200 feedback slot. Install tubing between the actuator casing and the appropriate DVC6200 pneumatic output port. If not already installed, install a vent in the port on the lower diaphragm casing.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Fisher Rotary Actuators 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while working on the equipment. Figure 10.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Quarter‐Turn Rotary Actuators The DVC6200 digital valve controller can be mounted to any quarter‐turn rotary actuator, as well as those that comply with the NAMUR guidelines. A mounting bracket and associated hardware are required. Refer to figure 12. 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 DVC6205 Remote Mount Base Unit Mounting For remote‐mounted digital valve controllers, the DVC6205 base unit ships separately from the control valve and does not include tubing, fittings or wiring. Pipestand Mounting 1. Position a standoff on the back of the base unit. 2. Using two 101.6 mm (4‐inch) 1/4‐20 hex head screws loosely attach the base unit to the pipestand with the mounting bracket. 3.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Wall Mounting 1. Install the wall mounting screws by using the mounting bracket as a template. 2. Install the mounting bracket to the back of the base unit using the spacers and screws provided in the mounting kit. 3. Slide the assembly on the wall mounting screws and tighten. 4. Proceed to Step 2—Connect the Pneumatic Tubing on page 15. Figure 15. FIELDVUE DVC6205 Wall Mounting 57 (2.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 SIS Step 2—Connect the Pneumatic Tubing Figure 16. Integral Mounting of a Fisher 67CFR Regulator on a FIELDVUE DVC6200 Digital Valve Controller OUTPUT A (1/4 NPT) 67CFR CAP SCREWS O‐RING NOTE: 1 APPLY LUBRICANT W9702-1 1 SUPPLY CONNECTION (1/4 NPT) OUTPUT B (1/4 NPT) 1. Connect the DVC6200 pneumatic output to the actuator input using at least 10 mm (3/8inch) diameter tubing.
DVC6200 Digital Valve Controllers January 2014 Quick Start Guide D103556X012 Check with an Emerson Process Management field office and industry instrument air quality standards for use with corrosive air or if you are unsure about the amount of air filtration or filter maintenance. When using natural gas as the supply medium, or for explosion proof applications, the following warnings also apply: D Remove electrical power before removing the housing cap.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 17. Vent Connection X0429 PLASTIC EXHAUST VENT (3/8 NPT) WARNING To avoid personal injury or property damage resulting from bursting or parts, do not exceed maximum supply pressure. Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and appropriate preventive measures are not taken.
DVC6200 Digital Valve Controllers January 2014 18 Quick Start Guide D103556X012
Quick Start Guide DVC6200 Digital Valve Controllers D103556X012 January 2014 SIS Step 3—Connect the Electrical Wires WARNING Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage from fire or explosion.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 FOUNDATION fieldbus or PROFIBUS PA Devices Refer to the DVC6200f instruction manual (D103412X012) or the DVC6200p instruction manual (D103563X012), available at www.FIELDVUE.com or from your local Emerson Process Management sales office for additional information. The digital valve controller is normally powered over the bus from a power supply.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 4. Make connections to the ground terminal(s) following national and local codes and plant standards. As shown in figure 19, two ground terminals are available for connecting a safety ground, earth ground, or drain wire. The safety ground terminal is electrically identical to the earth ground. 5. Replace and hand tighten the cover on the terminal box. 6.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 SIS HART Devices Refer to the DVC6200 HW1 instruction manual (D103409X012), the DVC6200 HW2 instruction manual (D103605X012), or the DVC6200 SIS instruction manual (D103557X012) available at www.FIELDVUE.com or from your local Emerson Process Management sales office for additional information. The digital valve controller is normally powered by a control system output channel.
Quick Start Guide D103556X012 DVC6200 Digital Valve Controllers January 2014 Note Depending on the control system you are using, an HF340 HART filter may be needed to allow HART communication. The HART filter is a passive device that is inserted in field wiring from the HART loop. The filter is normally installed near the field wiring terminals of the control system I/O.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 SIS Position Transmitter or Discrete Switch The DVC6200 HART communicating device has an optional output circuit that can be configured as a 420 mA position transmitter or a discrete switch. Configuration of the output circuit requires the proper DIP switch electrical setting on the main electronics board (figure 22) and also must be enabled with a user interface tool.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 23.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 SIS Remote Mount Feedback Unit The DVC6205 base unit is designed to receive a valve travel signal via the DVC6215 feedback unit. WARNING Do not place feedback wiring in the same conduit as other power or signal wiring. Personal injury or property damage, caused by wiring failure, can result if the feedback wiring connecting the base unit with the remote feedback unit shares a conduit with any other power or signal wiring.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 24.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Smart Wireless THUM Adapter Refer to the quick installation guide that comes with the Smart Wireless THUM Adapter (0082501004075) for additional information. Note The recommended mounting orientation for the THUM Adapter is vertically up, as shown in figure 26 for optimal wireless communication range. Figure 26. THUM Adapter Installed On DVC6200 Digital Valve Controller TOP CONDUIT ENTRANCE X0433 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 SIS Step 4—Configure the Digital Valve Controller WARNING D Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage from fire or explosion.
DVC6200 Digital Valve Controllers January 2014 Quick Start Guide D103556X012 2. Apply pneumatic supply pressure to the digital valve controller and adjust the supply pressure regulator according to the actuator requirements and limitations. 3. Apply electrical power to the digital valve controller. 4. Establish communication with the digital valve controller and commission the instrument as described in the host system documentation.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 SIS Special Instructions for Safety Instrumented Systems DVC6200 SIS instruments are identified by an SIS label on the terminal box cover. Please refer to the Safety Manual (D103601X012) for further information regarding the design, installation, and operation of the DVC6200 SIS product. The following section illustrates typical installation scenarios for a DVC6200 SIS.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 An optional local control panel (LCP100), shown in figure 29, can be installed to provide manual operation of the DVC6200 SIS instrument. Refer to the instruction manual that comes with the LCP100 for further information (D103272X012).
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 De-Energize to Trip (DETT) DVC6200 SIS and DETT Solenoid Valve In a typical deenergize to trip application with a solenoid valve, the logic solver (or DCS) trip signal deenergizes the solenoid valve and also reduces the signal to the digital valve controller to 4 mA (or 0 VDC). This opens the solenoid valve vent and drives the digital valve controller to the no output pressure condition.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 3. If the DVC6200 SIS and solenoid valve are powered separately: D Connect the logic solver output card +/ terminals to the corresponding solenoid valve +/ wires. D Connect the logic solver (or DCS) output card +/ terminals to the corresponding DVC6200 SIS LOOP +/ D terminals.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 De-Energize to Trip (DETT) DVC6200 SIS, no Solenoid Valve In a typical deenergize to trip application without a solenoid valve, the logic solver trip signal deenergizes the digital valve controller to 4 mA (or 0 VDC). This drives the digital valve controller to the no output pressure condition. As a result, the safety valve moves to its noair, fail safe position. Figure 32.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 2. If the DVC6200 SIS and solenoid valve are powered together: D Install an LC340 line conditioner to allow HART communication over the segment. Refer to the instruction D manual that comes with the LC340 (D102797X012) for more information. D Connect the logic solver output card +/ terminals to the corresponding LC340 SYS +/ terminals.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 DVC6200 SIS for PST only and De-Energize to Trip (DETT) Solenoid Valve In this application, the logic solver trip signal deenergizes the solenoid valve, which opens the solenoid vent valve. The DVC6200 SIS is configured as energize to trip (ETT) and uses a reverse acting relay (Relay B) to drive the digital valve controller to the no output pressure condition.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Solenoid Valve Health Monitoring If a solenoid valve is installed between the DVC6200 SIS pressure output and the actuator, the control valve assembly can be configured to verify the operation of the solenoid valve. This applies to singleacting actuator applications only. The “unused” output port of the DVC6200 SIS is tubed such that the pressure downstream of the solenoid valve is measured.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 SIS Hazardous Area Approvals and Special Instructions for “Safe Use” and Installations in Hazardous Locations Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval type.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 CSA Ordinary Locations Approval Complies with general electrical safety CAN/CSAC22.2 No. 6101012004 SELV, conduit connected, Enclosure Type 4X, IP66, Installation Category I, Pollution Degree 4 DVC6200 Series (HART HW1, FOUNDATION fieldbus, PROFIBUS) Rated Input 9-30 VDC, 4-20 mA -52_C to + 80_C Ambient DVC6205 (HART HW1, FOUNDATION fieldbus, PROFIBUS) DVC6215 Remote Mount Rated Input 9-30 VDC, 4-20 mA Rated Input 10 VDC max, 3.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Intrinsically Safe Class I, Division 1, Groups A,B,C,D Class II, Division 1, Groups E,F,G Class III, Division 1 Ex ia IIC Type 4X, IP66 Single Seal Device (HART HW2 and SIS pending) Rated input 30 V DC max, 20 mA - 52 _C < Ambient < + 80_C (-52_C to 125_C for DVC6215) Max inlet pressure 145 psig (air or natural gas) Intrinsically safe when connected per installation drawing GE42818, as shown in the following figures DVC6200 HW1
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 38. CSA Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III HW2 - WITH OR WITHOUT I/O PACKAGE DVC6200, DVC6200S LOOP TERMINALS Vmax = 30 VDC Imax = 130 mA Ci = 15 nF Li = 0.55 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 39.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 40. CSA Loop Schematics—FIELDVUE DVC6200f and DVC6200p HAZARDOUS LOCATION T CODE CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III T (amb) T4 ≤ 80_C T5 ≤ 77_C T6 ≤ 62_C NON‐HAZARDOUS LOCATION DVC6200F, DVC6200FS DVC6200P, DVC6200PS Vmax = 24 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 41. CSA Loop Schematics FIELDVUE DVC6205f, DVC6205p, and DVC6215 HAZARDOUS LOCATION CSA APPROVED ENTITY DEVICE CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III DVC6215 Vmax = 30 VDC Imax = 226 mA Ci = 50 nF Li = 0.55 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 42. Notes for CSA Loop Schematics THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION.
Quick Start Guide DVC6200 Digital Valve Controllers January 2014 D103556X012 FM Explosion-proof, Dust-Ignition proof, Non-Incendive, Suitable for Use DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, FOUNDATION FIELDBUS, PROFIBUS) XP: Class I, Division 1, Groups B,C,D DIP: Class II, III, Division 1, Groups E,F,G NI: Class I, Division 2, Groups A,B,C,D S: Class II, III, Division 2, Groups F,G T5 Ta = 80°C, T6 Ta = 75°C Type 4X, IP66 DVC6215 Remote Mount XP: Class I, Division 1, Groups A,B,C,D DIP: Class II
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 43. FM Loop Schematic—FIELDVUE DVC6200 HW1 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION I.S. CLASS I,II,III, DIV 1, GROUPS ABCDEFG N.I. CLASS I, DIV 2, GROUPS ABCD DVC6200, DVC6200S Vmax = 30 VDC Imax = 226 mA Ci = 5 nF Li = 0.55 mH Pi = 1.4 W FM APPROVED BARRIER 1 NOTE 1, 3, 4, 5, 6 T CODE T (amb) T5 ≤ 80_C T6 ≤ 75_C 1 SEE NOTES IN FIGURE 48 GE42819 sheet 2, Rev.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 44. FM Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION I.S. CLASS I, II, III DIV 1, GROUPS ABCDEFG N.I. CLASS I, DIV 2, GROUPS ABCD HW2 - WITH OR WITHOUT I/O PACKAGE DVC6200, DVC6200S LOOP TERMINALS Vmax = 30 VDC Imax = 130 mA Ci = 15 nF Li = 0.55 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 45. FM Loop Schematics FIELDVUE DVC6205, DVC6205 SIS, and DVC6215 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION I.S. CLASS I, II, III DIV 1, GROUPS ABCDEFG N.I. CLASS I, DIV 2, GROUPS ABCD HW2 - WITH OR WITHOUT I/O PACKAGE DVC6205 FIELD WIRING TERMINAL BOX REMOTE FIELD WIRING TERMINAL BOX I.S. CLASS I, II, III DIV 1, GROUPS ABCDEFG N.I.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 46. FM Loop Schematics—FIELDVUE DVC6200f and DVC6200p HAZARDOUS LOCATION T CODE I.S. CLASS I,II,III DIV 1, GROUPS ABCDEFG N.I. CLASS I, DIV 2, GROUPS ABCD T (amb) T4 ≤ 80_C T5 ≤ 77_C T6 ≤ 62_C NON‐HAZARDOUS LOCATION DVC6200F, DVC6200FS DVC6200P, DVC6200PS Vmax = 24 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 47. FM Loop Schematics FIELDVUE DVC6205f, DVC6205p, and DVC6215 HAZARDOUS LOCATION I.S. CLASS I, II, III DIV 1, GROUPS ABCDEFG N.I. CLASS I, DIV 2, GROUPS ABCD DVC6215 Vmax = 30 VDC Imax = 226 mA Ci = 50 nF Li = 0.55 mH Pi = 1.4 W FM APPROVED ENTITY DEVICE NON‐HAZARDOUS LOCATION I.S. CLASS I, II, III DIV 1, GROUPS ABCDEFG N.I.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 48. Notes for FM Loop Schematics THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION.
DVC6200 Digital Valve Controllers January 2014 D103556X012 ATEX Flameproof II 2 G WARNING Do not open while energized. Potential electrostatic charging hazard. See warning on page 2. DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, FOUNDATION FIELDBUS, PROFIBUS) Ex d IIC T5 (Ta ≤ 85°C) Ex d IIC T6 (Ta ≤ 80°C) Operating ambient temperature Standard construction -40_C to +85_C, Extreme temperature construction -52_C to +85_C Type n II 3 G WARNING Do not open while energized.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Intrinsically safe when connected per control drawing GE60771, as shown in the following figures DVC6200 HW1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . figure 49 and 54 DVC6200 HW2, DVC6200 SIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . figure 50 and 54 DVC6205, DVC6205 SIS, and DVC6215 Remote Mount . . . . . . . . figure 51 and 54 DVC6200f and DVC6200p . . . . . . .
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 50. ATEX Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 0, Ex ia IIC ZONE 20, Ex ia IIIC HW2 - WITH OR WITHOUT I/O PACKAGE DVC6200, DVC6200S LOOP TERMINALS Ui = 30 VDC Ii = 130 mA Ci = 15 nF Li = 0.55 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 51. ATEX Loop Schematics FIELDVUE DVC6205, DVC6205 SIS, and DVC6215 HAZARDOUS LOCATION ZONE 0, Ex ia IIC ZONE 20, Ex ia IIIC ZONE 0, Ex ia IIC HW2 - WITH OR WITHOUT I/O PACKAGE DVC6205 DVC6215 T CODE T AMB T4 ≤ 125_C T5 T6 ≤ 95_C ≤ 80_C NON‐HAZARDOUS LOCATION REMOTE FIELD WIRING TERMINAL BOX FIELD WIRING TERMINAL BOX LOOP TERMINALS ZONE 0, Ex ia IIC Ui = 30 VDC Ii = 130 mA Ci = 15 nF Li = 0.55 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 52. ATEX Loop Schematics—FIELDVUE DVC6200f and DVC6200p ZONE 0 Ex ia IIC T CODE ZONE 20 Ex ia IIIC T AMB MAX SURFACE TEMP HAZARDOUS LOCATION T AMB T4 ≤ 80_C T103_C T5 ≤ 77_C T100_C ≤ 77_C T6 ≤ 62_C T85_C ≤ 62_C NON‐HAZARDOUS LOCATION ZONE 0, Ex ia IIC ZONE 20, Ex ia IIIC ≤ 80_C DVC6200F, DVC6200FS DVC6200P, DVC6200PS Ui = 24 VDC Ii = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 53. ATEX Loop Schematics FIELDVUE DVC6205f, DVC6205p, and DVC6215 HAZARDOUS LOCATION ZONE 0, Ex ia IIC ZONE 20, Ex ia IIIC DVC6205f, DVC6205p ZONE 0, Ex ia IIC ATEX APPROVED ENTITY DEVICE NOTE 1, 3 1 NON‐HAZARDOUS LOCATION DVC6215 Ui = 30 VDC Ii = 226 mA Ci = 50 nF Li = 0.55 mH Pi = 1.4 W Ui = 24 VDC Ii = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.4 W Uo = 24 VDC Io = 44 mA Ca = 121 nF La = 30 mH Po = 0.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 54. Notes for ATEX Loop Schematics THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION.
Quick Start Guide DVC6200 Digital Valve Controllers D103556X012 January 2014 IECEx Flameproof WARNING Do not open while energized. Potential electrostatic charging hazard. See warning on page 2. DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, FOUNDATION FIELDBUS, PROFIBUS) Ex d IIC T5 (Ta ≤ 80°C) / T6 (Ta ≤ 75°C) 30 V max, 20 mA IP66 DVC6215 Remote Mount Ex d IIC T4 (Ta ≤ 125_C) / T5 (Ta ≤ 95_C) / T6 (Ta ≤ 80_C) 30 V max, 20 mA IP66 Type n WARNING Do not open while energized.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Intrinsically Safe WARNING Potential electrostatic charging hazard. See warning on page 2. Ex ia IIC IP66 Intrinsically safe when connected per drawing GE42990, as shown in the following figures DVC6200 HW1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . figure 55 and 60 DVC6200 HW2 and DVC6200 SIS . . . . . . . . . . . . . . . . . . . . . . . . . . .
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 56. IECEx Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 0, Ex ia IIC HW2 - WITH OR WITHOUT I/O PACKAGE DVC6200, DVC6200S LOOP TERMINALS Vmax = 30 VDC Imax = 130 mA Ci = 15 nF Li = 0.55 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 57. IECEx Loop Schematics FIELDVUE DVC6205, DVC6205 SIS, and DVC6215 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 0, Ex ia IIC HW2 - WITH OR WITHOUT I/O PACKAGE DVC6205 REMOTE FIELD WIRING TERMINAL BOX FIELD WIRING TERMINAL BOX LOOP TERMINALS ZONE 0, Ex ia IIC Vmax = 30 VDC Imax = 130 mA Ci = 15 nF Li = 0.55 mH Pi = 1.0 W DVC6215 Vmax = 30 VDC Imax = 226 mA Ci = 50 nF Li = 0.55 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 58. IECEx Loop Schematics—FIELDVUE DVC6200f and DVC6200p T CODE T (amb) T4 ≤ 80_C T5 ≤ 77_C T6 ≤ 62_C HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 0, Ex ia IIC DVC6200F, DVC6200FS DVC6200P, DVC6200PS Ui = 24 VDC Ii = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.4 W IECEx APPROVED ENTITY DEVICE NOTE 1, 3 1 IECEx APPROVED BARRIER 1 NOTE 5 1 NOTE 1, 3, 4 GE42990 Sheet 3, Rev.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 59. IECEx Loop Schematics FIELDVUE DVC6205f, DVC6205p, and DVC6215 HAZARDOUS LOCATION ZONE 0, Ex ia IIC IECEx APPROVED ENTITY DEVICE NOTE 1, 3 1 DVC6215 Ui = 30 VDC Ii = 226 mA Ci = 50 nF Li = 0.55 mH Pi = 1.4 W NOTE 1 1 NON‐HAZARDOUS LOCATION ZONE 0, Ex ia IIC DVC6205f, DVC6205p Uo = 24 VDC Io = 44 mA Ca = 121 nF La = 30 mH Po = 0.33 W Ui = 24 VDC Ii = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.
DVC6200 Digital Valve Controllers Quick Start Guide January 2014 D103556X012 Figure 60. Notes for IECEx Loop Schematics THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION.
DVC6200 Digital Valve Controllers January 2014 Quick Start Guide D103556X012 Scan the appropriate QR code for digital valve controller field support Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.