Instruction Manual

Instruction Manual
D103412X012
Introduction and Specifications
January 2015
7
Table 1‐1. Specifications
Available Mounting
DVC6200f digital valve controller and DVC6215
feedback unit:
Integral mounting to the Fisher GX
Control Valve and Actuator System
Integral
mounting to Fisher rotary actuators,
Sliding‐stem
linear applications
Quarter‐turn rotary applications
DVC6205f base unit for 2 inch pipestand or wall
mounting (for remote-mount)
The DVC6200f digital valve controller or DVC6215
feedback unit can also be mounted on other
actuators that comply with IEC 60534-6-1, IEC
60534-6-2, VDI/VDE 3845 and NAMUR mounting
standards.
Function Block Suites
Standard Control (throttling control)
 Includes AO, PID, ISEL, OS, AI, MAI, DO,
 and four DI function block
Fieldbus Control (throttling control)
 Contains the AO function block
Fieldbus Logic [discrete (on/off) connectivity]
 Includes DO, and four DI function blocks
Block Execution Times
AO Block: 15 ms AI Block: 15 ms
PID Block: 20 ms MAI BLock: 35 ms
ISEL Block: 20 ms DO Block: 15 ms
OS Block: 20 ms DI Block: 15 ms
Electrical Input
Voltage Level: 9 to 32 volts
Maximum Current: 19 mA
Reverse Polarity Protection: Unit is not polarity
sensitive
Termination: Bus must be properly terminated per
ISA SP50 guidelines
Digital Communication Protocol
F
OUNDATION fieldbus registered device
Physical Layer Type(s):
121—Low-power signaling, bus‐powered,
Entity Model I.S.
511—Low-power signaling, bus‐powered, FISCO I.S.
Fieldbus Device Capabilities
Backup Link Master capable
Supply Pressure
(1)
Minimum Recommended: 0.3 bar (5 psig) higher
than maximum actuator requirements
Maximum: 10.0 bar (145 psig) or maximum pressure
rating of the actuator, whichever is lower
Supply Medium
Air or natural gas
Air: Supply pressure must be clean, dry air that meets
the requirements of ISA Standard 7.0.01.
Natural Gas: Natural gas must be clean, dry, oil‐free,
and noncorrosive. H
2
S content should not exceed 20
ppm.
A maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to 5
micrometer particle size is recommended. Lubricant
content is not to exceed 1 ppm weight (w/w) or
volume (v/v) basis. Condensation in the air supply
should be minimized.
Per ISO 8573-1
Maximum particle density size: Class 7
Oil content: Class 3
Pressure Dew Point: Class 3 or at least 10 K less than
the lowest ambient temperature expected
Output Signal
Pneumatic signal, up to full supply pressure
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action:
Double, Single Direct or Reverse
Steady-State Air Consumption
(2)(3)
Standard Relay: At 1.4 bar (20 psig) supply pressure:
Less than 0.38 normal m
3
/hr (14 scfh)
At 5.5 bar (80 psig) supply pressure: Less than 1.3
normal m
3
/hr (49 scfh)
Low Bleed Relay: At 1.4 bar (20 psig) supply pressure:
Average value 0.056 normal m
3
/hr
(2.1 scfh)
At 5.5 bar (80 psig) supply pressure: Average value
0.184 normal m
3
/hr (6.9 scfh)
Maximum Output Capacity
(2)(3)
At 1.4 bar (20 psig) supply pressure: 10.0 normal m
3
/hr
(375 scfh)
At 5.5 bar (80 psig) supply pressure: 29.5 normal m
3
/hr
(1100 scfh)
-continued-