Introduction
January 2015
7
Table 1‐2. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level
Performance
Criteria
(1)
Enclosure
Electrostatic discharge (ESD) IEC 61000‐4‐2
4 kV contact
8 kV air
A
Radiated EM field IEC 61000‐4‐3
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
A
Rated power frequency
magnetic field
IEC 61000‐4‐8 30 A/m at 50/60Hz A
I/O signal/control
Burst IEC 61000‐4‐4 1 kV A
Surge IEC 61000‐4‐5 1 kV B
Conducted RF IEC 61000‐4‐6 150 kHz to 80 MHz at 3 Vrms A
Performance criteria: +/- 1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
Related Documents
This section lists other documents containing information related to the DVC6200 SIS digital valve controller. These
documents include:
DBulletin 62.1:DVC6200 SIS - Fisher FIELDVUE DVC6200 SIS Digital Valve Controller (D103555X012)
DBulletin 62.1:DVC6200(S1) Fisher FIELDVUE DVC6200 Digital Valve Controller Dimensions (D103543X012)
DFisher FIELDVUE DVC6200 Series Digital Valve Controller Quick Start Guide (D103556X012)
DFIELDVUE DVC6200 SIS Safety Manual (D103601X012)
DHART Field Device Specification for FIELDVUE DVC6200 SIS (D103638X012)
DPartial Stroke Test using 475/375 Field Communicator (D103320X012)
DPartial Stroke Test using ValveLink Software (D103274X012)
DPre-Commissioning Installation / Setup Guidelines using ValveLink Software (D103285X012)
DBulletin 62.1:LCP100 (D103604X012)
DFisher LCP100 Instruction Manual (D103272X012)
DFisher LC340 Instruction Manual (D102797X012)
DFisher HF340 Filter Instruction Manual (D102796X012)
D475 Field Communicator User's Manual
D ValveLink Software Help or Documentation
All documents are available from your Emerson Process Management sales office. Also visit our website at
www.FIELDVUE.com.