Instruction Manual

Instruction Manual
D103557X012
Device Information, Diagnostics, and Alerts
January 2015
54
DLocal Control Panel
The LCP100 local control panel is wired directly to the DVC6200 SIS digital valve controller.
The black “Valve Test” push button (see figure 5‐3) allows the valve to perform the configured partial stroke test.
- Press and hold for 3 to 10 seconds
The test can be overridden by the “Valve Close” button, “Valve Open” button, or if an emergency demand occurs.
Figure 5‐3. Local Control Panel
PRESS TO PERFORM THE
CONFIGURED PARTIAL
STROKE TEST
DField Communicator
1. Connect the Field Communicator to the LOOP terminals on the digital valve controller.
2. Turn on the Field Communicator.
3. From the Online menu, select Service Tools > Diagnostics > Partial Stroke Test.
4. Select either Standard (10%) or Custom. With the Custom Stroke Test, the stroke may be entered up to 30% with
configurable stroking speed and pause time.
5. The currently configured Stroke, Stroking Speed, and Pause Time is displayed. Choose “Yes” to run the test using
these values. Choose “No” to modify the values. The default value for Stroke Speed is 0.25%/second.
6. The valve begins to move and the actual travel reported by the digital valve controller is displayed on the Field
Communicator.
7. Once the valve has reached the endpoint, check that the valve has reached the desired set point. The valve should
return to its original position.