Configuration
January 2015
17
Section 3 Configuration
Guided Setup
Field Communicator Configure > Guided Setup (2‐1)
To quickly setup the instrument, the following procedures will guide you through the process.
DDevice SetupThis procedure is used to configure actuator and valve information, calibrate the valve assembly, and
assign the tuning set for the valve assembly.
DPerformance TunerThis procedure executes a simple step response test and then calculates a recommended set of
gain values based on the response of the control valve. See page 24 for additional information.
Manual Setup33
Manual Setup allows you to configure the digital valve controller to your application. Table 3‐1 lists the default settings
for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel
cutoffs and limits. You can also restart the instrument and set the protection.
Refer to table 3‐2 for possible configurations for a digital valve controller operated by a 4‐20 mA input current
(point‐to‐point mode), and table 3‐3 for possible configurations for a digital valve controller operated by a 0‐24 VDC
power supply (multi‐drop mode).
Table 3‐1. Default Detailed Setup Parameters
Setup Parameter Default Setting
(1)
Instrument
Configuration
Restart Control Mode Resume Last
Polling Address 0
Burst Mode Enable No
Burst Command 3
Dynamic Response and
Tuning
Input Characterization Linear
Travel Limit High 125%
Travel Limit Low -25%
Travel/Pressure Cutoff High 50%
Travel/Pressure Cutoff Low 50%
Integrator Enable Yes
Integral Gain 9.4 repeats/minute
Integral Deadzone 0.26%
Deviation & Other Alerts
Travel Deviation Alert Enable Yes
Travel Deviation Alert Point 5%
Travel Deviation Time 9.99 sec
Pressure Deviation Alert Enable Yes
Pressure Deviation Alert Point 5 psi
(2)
Pressure Deviation Alert Time 9.99 sec
Drive Signal Alert Enable Yes
Supply Pressure Alert Enable Yes
1. The settings listed are for standard factory configuration. DVC6200 SIS instruments can also be ordered with custom configuration
settings. Refer to the order requisition for custom settings.
2. Adjust to bar, kPa, or Kg/cm
2
if necessary.