Instruction Manual
Instruction Manual
D103557X012
Wiring Practices
January 2015
16
Figure 2‐5. Wiring for Loop‐Powered Configuration; Logic Solver Wired to the FIELDVUE DVC60200 SIS then the
Fisher LCP100
NOTE:
1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE AT LEAST 8 mA.
THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES
APPROXIMATELY 4 mA.
SWITCH
TO LOOP
POSITION
8‐20 mA
(USER SUPPLIED)
AUX )
LOOP )
LOOP *
CASE GROUND
DVC6200 SIS TERMINAL BOX
SHIELD NOT CONNECTED TO LCP100
LCP100
LOGIC SOLVER
OUTPUT
1
POINT‐TO‐POINT MODE
NOTE:
1 THE LCP100, WHEN POWERED BY THE LOOP,
CONSUMES APPROXIMATELY 4 mA.
SWITCH
TO LOOP
POSITION
24VDC
)
(USER SUPPLIED)
CASE GROUND
DVC6200 SIS
TERMINAL BOX
SHIELD NOT CONNECTED TO LCP100
LCP100
*
LOGIC SOLVER
OUTPUT
1
MULTI‐DROP MODE
AUX )
LOOP )
LOOP *
THE DVC6200 SIS MUST BE
IN POINT‐TO‐POINT MODE
THE DVC6200 SIS MUST
BE IN MULTI‐DROP MODE
LC340 LINE
CONDITIONER
SYS - /)
FLD - /)
LOOP
LOOP
E1468
E1469