D103557X012
Wiring Practices
January 2015
15
Figure 2‐4. Wiring for Loop‐Powered Configuration; Logic Solver Wired to the Fisher LCP100 then the
FIELDVUE DVC6200 SIS
NOTE:
1 THE LOGIC SOLVER MINIMUM
OUTPUT MUST BE AT LEAST 8 mA. THE
LCP100, WHEN POWERED BY THE LOOP,
CONSUMES APPROXIMATELY 4 mA.
AUX )
LOOP )
LOOP *
SWITCH TO
LOOP POSITION
CASE GROUND
SHIELD NOT CONNECTED
TO LCP100
DVC6200 SIS TERMINAL BOX
LCP100
LOGIC SOLVER
OUTPUT
1
(USER SUPPLIED)
THE DVC6200 SIS MUST BE
IN POINT‐TO‐POINT MODE
LOOP
8‐20 mA
NOTE:
1 THE LCP100, WHEN POWERED BY THE LOOP,
CONSUMES APPROXIMATELY 4 mA.
AUX )
LOOP )
LOOP *
SWITCH TO
LOOP POSITION
CASE GROUND
SHIELD NOT CONNECTED TO LCP100
DVC6200 SIS TERMINAL BOX
LCP100
24VDC
LOGIC SOLVER
OUTPUT
1
(USER SUPPLIED)
SYS - /)
FLD - /)
THE DVC6200 SIS MUST
BE IN MULTI‐DROP MODE
POINT‐TO‐POINT MODE
MULTI‐DROP MODE
LC340 LINE
CONDITIONER
LOOP
E1466
E1467