Instruction Manual

Instruction Manual
D103557X012
Wiring Practices
January 2015
14
Figure 2‐3. Wiring for 24 VDC External Power Configuration
NOTE: DO NOT CONNECT THE LOOP + TERMINAL IN THE LCP100 TO THE LOOP + TERMINAL IN THE DVC6200 SIS.
THIS WILL CAUSE THE LCP100 TO UNNECESSARILY CONSUME 4 mA AT THE EXPENSE OF THE DVC6200 SIS.
SIMPLE METHOD FOR INSTALLING AN LCP100 TO AN EXISTING
DVC6200 SIS INSTRUMENT WHEN 24 VDC POWER IS AVAILABLE
SWITCH TO
24VDC POSITION
24 VDC
(USER SUPPLIED)
4‐20 mA
AUX )
AUX*
CASE GROUND
SHIELD NOT CONNECTED TO LCP100
24VDC )
DVC6200 SIS TERMINAL BOX
LCP100
SOURCE
24VDC *
1
1 THIS CONNECTION IS ALSO LABELED LOOP -.
LOGIC
SOLVER
OUTPUT
24VDC
(USER SUPPLIED)
E1465