Instruction Manual

Detailed Setup
September 2013
4-15
ALERT IS CLEARED
ALERT IS SET
TRAVEL ALERT
HIGH POINT
TRAVEL ALERT
DEADBAND
A6532/IL
Figure 4-2. Travel Alert Deadband
Travel Limit Alerts (1-2-3-4-5)
Travel Alert Hi Hi is set if the ranged travel rises above
the alert high point. Once the alert is set, the ranged
travel must fall below the alert high high point by the
Travel Alert Deadband before the alert is cleared. See
figure 4-2.
Travel Alert Lo Lo is set if the ranged travel falls below
the alert low low point. Once the alert is set, the
ranged travel must rise above the alert low low point
by the Travel Alert Deadband before the alert is
cleared.
Travel Alert Hi Hi Enable—Yes or No. Activates
checking of the ranged travel against the Travel Alert
High-High points.
Travel Alert Lo Lo Enable—Yes or No. Activates
checking of the ranged travel against the Travel Alert
Low-Low points.
Travel Alert Hi Hi Point—The value of the travel,
in percent (%) of ranged travel, which, when
exceeded, sets the Travel Alert Hi Hi alert. When used
with the LCP100 local control panel this value is
defaulted to 99% (< 99% travel, flashing light, > 99%
travel, solid lights).
Travel Alert Lo Lo Point—The value of the travel,
in percent (%) of ranged travel, which, when
exceeded, sets the Travel Alert Lo Lo alert. When
used with the LCP100 local control panel the value is
set to 1%.
Travel Limit Hi/Lo Alerts (1-2-3-4-6)
Travel Alert Hi is set if the ranged travel rises above
the alert high point. Once the alert is set, the ranged
travel must fall below the alert high point by the Travel
Alert Deadband before the alert is cleared. See figure
4-2.
Travel Alert Lo is set if the ranged travel falls below
the alert low point. Once the alert is set, the ranged
Deadband Reference
Deadband (+/ 5%)
Deadband exceeded, and direction
changed, new Reference Point
established
Point
Point at which
cycle is counted.
A6533-1/IL
Figure 4-3. Cycle Counter Deadband (set at 10%)
travel must rise above the alert low point by the Travel
Alert Deadband before the alert is cleared.
Travel Alert Hi Enable—Yes or No. Activates
checking of the ranged travel against the Travel Alert
High Point.
Travel Alert Lo Enable—Yes or No. Activates
checking of the ranged travel against the Travel Alert
Lo Point.
Travel Alert Hi Point—The value of the travel, in
percent (%) of ranged travel, which, when exceeded,
sets the Travel Alert High alert.
Travel Alert Lo Point—The value of the travel, in
percent (%) of ranged travel, which, when exceeded,
sets the Travel Alert Low alert.
Travel Limit/Cutoff Alerts (1-2-3-4-7)
Travel Limit/Cutoff Hi Enable—Yes or No.
Activates the Travel Limit/Cutoff Hi alert.
Travel Limit/Cutoff Lo Enable—Yes or No.
Activates the Travel Limit/Cutoff Lo alert.
Cutoff Hi—Defines the high cutoff point for the
travel in percent (%) of pre-characterized set point.
Cutoff Lo—Defines the low cutoff point for the
travel in percent (%)of pre-characterized set point.
Change Cutoffs—Allows you to set Cutoff Hi and
Cutoff Lo. When a cutoff is set the corresponding
travel or pressure limit is disabled.
Travel History Alerts
Cycle Counter (1-2-3-5-1)
Cycle Count Alert Enable—Yes or No. Activates
checking of the difference between the Cycle Counter
4