Instruction Manual
Detailed Setup
September 2013
4-7
Table 4-3. Conditions for Modifying FIELDVUE DVC6000 SIS Digital Valve Controller Parameters (Continued)
Parameters
In Service Out of Service
Protected Unprotected Protected Unprotected
Valve & Actuator
Relay Type
Zero Power Condition
Maximum Supply Pressure
Auxiliary Terminal Action
Instrument Date and Time
Last Calibration Status
(1)
Calibration Location
(1)
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
Manufacturer
(1)
Valve Serial Number
Valve Style
Actuator Style
View/Edit Feedback Connection
Travel Sensor Motion
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
SIS / Partial
Stroke
Partial Stroke Test Enable
Partial Stroke Press Limit
Maximum Travel Movement
Test Speed
Test Pause Time
View/Edit Auto Test Interval
Device Power Up
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
—indicates parameter may be modified for instrument mode and protection shown.
1. Information only.
Note
When selecting a tuning set for a
DVC6015, DVC6025 or DVC6035 remote
mount unit, it may be necessary to
reduce the tuning set, due to the
effects of the long tubing between the
digital valve controller and the
actuator.
Note
Use Expert tuning only if standard
tuning has not achieved the desired
results.
Stabilize/Optimize or Performance
Tuner may be used to achieve the
desired results more rapidly than
Expert tuning.
Table 4-4 provides tuning set selection guidelines for
Fisher actuators. These tuning sets are only
recommended starting points. After you finish setting
up and calibrating the instrument, you may have to
select either a higher or lower tuning set to get the
desired response. You can use the Performance
Tuner to optimize tuning.
Integral Enable—Yes or No. Enable the integral
setting to improve static performance by correcting for
error that exists between the travel target and actual
travel. Travel Integral Control is disabled by default.
Integral Gain—Travel Integral Gain is the ratio
of the change in output to the change in input, based
on the control action in which the output is proportional
to the time integral of the input.
Stabilize/Optimize—Stabilize/Optimize permits
you to adjust valve response by changing the digital
valve controller tuning.
If the valve is unstable, select Decrease Response to
stabilize valve operation. This selects the next lower
tuning set (e.g., F to E). If the valve response is
sluggish, select Increase Response to make the valve
more responsive. This selects the next higher tuning
set (e.g., F to G).
If after selecting Decrease Response or Increase
Response the valve travel overshoot is excessive,
select Decrease Damping to select a damping value
that allows more overshoot. Select Increase Damping
to select a damping value that will decrease the
overshoot. When finished, select done.
4