Instruction Manual

DVC6000 SIS
September 2013
4-2
Detailed Setup
The Detailed Setup selection from the Configure menu
allows you to configure the digital valve controller to
your application. Table 4-1 lists the default settings for
a standard factory configuration. You can adjust
actuator response, set the various modes, alerts,
ranges, travel cutoffs and limits. You can also restart
the instrument and set the protection.
Note
In the event of a power failure the
DVC6000 SIS automatically restores
the device to In Service upon
restoration of power. This is to provide
greater availability of the safety
function.
If power is inadvertently interrupted
while performing set up or
maintenance, you may need to return
the DVC6000 SIS to out of service if
the interrupted task requires that mode
of operation.
Mode and Protection (1-2-1)
Mode
Instrument Mode
You can change the instrument mode by selecting
Mode and Protection, Instrument Mode from the
Detailed Setup menu, or press the Hot Key and select
Instrument Mode.
Instrument Mode allows you to either take the
instrument Out Of Service or place it In Service.
Taking the instrument Out Of Service allows you to
perform instrument calibration and also allows you to
change setup variables that affect control, provided
the calibration/configuration protection is properly set.
See Setting Protection.
Table 4-1. Factory Default Detailed Setup Parameters
Setup Parameter Default Setting
(1)
Instrument
Configuration
Control Mode Analog / Digital
(2)
Restart Control Mode
(3)
Multi-drop
Point-to-Point
DIGITAL
ANALOG
Zero Power Condition Valve Closed
(2)
Analog In Range Low 4 mA
Analog In Range High 20 mA
Analog Input Units mA
Feedback Connection Rotary All
(2)
Travel Sensor Motion Clockwise
(2)
Auxiliary Terminal Action
Push Button Partial
Stroke Test
Maximum Supply Pressure 50
(2)
Pressure Units PSI
Temperature Units F
Polling Address 0
Burst Mode Enable No
Burst Command 3
Cmd 3 Configured Pressure
For double-acting actuators
For single-acting actuators
differential output
pressure
actuator pressure
Dynamic
Response and
Tuning
Tuning Set F
(2)
Input Characteristic Linear
Travel Limit High 125%
Travel Limit Low 25%
Travel/Pressure Cutoff High 50%
Travel/Pressure Cutoff Low 50%
Set Point Rate Open
(4)
0%/sec
Set Point Rate Close
(5)
0%/sec
Set Point Filter Lag Time 0 sec
Partial Stroke Start Point Valve Open
(2)
Travel History
Alerts
Cycle Count Alert Enable No
Cycle Count Alert Deadband 1%
Cycle Count Alert Point 1000000
Travel Accumulator Alert
Enable
No
Travel Accumulator Deadband 1%
Travel Accumulator Alert Point 1000000%
Deviation &
Other Alerts
Travel Deviation Alert Enable Yes
Travel Deviation Alert Point 5%
Travel Deviation Time 10 sec
Pressure Deviation Alert
Enable
Yes
Pressure Deviation Alert Point 5 psi
Pressure Deviation Alert Time 30 sec
Drive Signal Alert Enable Yes
Supply Pressure Alert Enable Yes
Supply Pressure Alert Point 19 psi
Travel Alerts
Travel Alert Lo Enable No
Lo Point 25%
Travel Alert Hi Enable No
Hi Point 125%
Travel Alert Lo Lo Enable No
Lo Lo Point 25%
(6)
Travel Alert Hi Hi Enable
No
Hi Hi Point 125%
(7)
Deadband 5%
continued on next page
4