Instruction Manual

DVC6000 SIS
September 2013
3-4
Table 3-1. Possible Configurations for a FIELDVUE DVC6000 SIS Digital Valve Controller operated by 4-20 mA
Setup Wizard Configuration Operating Conditions Status Monitoring
Relay Type
Partial Stroke
Start Point
Zero Power
Condition
Input Current Actual Valve Travel
Travel Set
Point
Travel
A or C
Open
Close
Common Application
20 mA Open 100% 100%
Open
Less Common Application
4 mA Open 100% 100%
Close
Close
Less Common Application
4 mA Close 0% 0%
Open
Common Application
20 mA Close 0% 0%
B
Open
Close
Less Common Application
20 mA Open 100% 100%
Open
Common Application
4 mA Open 100% 100%
Close
Close
Common Application
4 mA Close 0% 0%
Open
Less Common Application
20 mA Close 0% 0%
Table 3-2. Possible Configurations for a FIELDVUE DVC6000 SIS Digital Valve Controller operated by 0-24 VDC
Setup Wizard Configuration Operating Conditions Status Monitoring
Relay Type
Partial Stroke
Start Point
Zero Power
Condition
Power Supply Actual Valve Travel
Travel Set
Point
Travel
A or C
Open
Close
Common Application
24 VDC Open 100% 100%
Open
(1)
Less Common Application
24 VDC Open 100% 100%
Close
Close
(1)
Less Common Application
24 VDC Close 0% 0%
Open
Common Application
24 VDC Close 0% 0%
B
Open
Close
Less Common Application
24 VDC Open 100% 100%
Open
(1)
Common Application
24 VDC Open 100% 100%
Close
Close
(1)
Common Application
24 VDC Close 0% 0%
Open
Less Common Application
24 VDC Close 0% 0%
1. In these configurations, the DVC6000 SIS is used as a diagnostic device, the safety function is provided by other devices in the pneumatic loop, e.g. a solenoid valve.
Note
The use of a Quick Exhaust Valve
(QEV) is not recommended for safety
instrumented system applications. The
use of a QEV in an SIS application may
cause the valve to cycle.
11. Specify if factory defaults should be used for
setup. If you select YES for factory default, the Field
Communicator sets the setup parameters to the
values listed in table 3-3. If you select NO for the
factory defaults, the setup parameters listed in the
table remain at their previous settings.
Typically the Setup Wizard determines the required
setup information based upon the actuator
manufacturer and model specified. However, if you
enter other for the actuator manufacturer or the
3