Instruction Manual

Basic Setup
September 2013
3-3
Note
In the event of a power failure the
DVC6000 SIS automatically restores
the device to In Service upon
restoration of power. This is to provide
greater availability of the safety
function.
If power is inadvertently interrupted
while performing set up or
maintenance, you may need to return
the DVC6000 SIS to out of service if
the interrupted task requires that mode
of operation.
When the DVC6000 SIS digital valve controller is
ordered as part of a control valve assembly, the
factory mounts the digital valve controller and sets up
the instrument as specified on the order. When
mounting to a valve in the field, the instrument needs
to be set up to match the instrument to the valve and
actuator.
Before beginning Guided Setup, be sure the
instrument is correctly mounted as described in the
Installation section.
Setup Wizard (1-1-1)
Note
The Setup Wizard must be run for first
time installations before placing the
DVC6000 SIS in service.
Use the Setup Wizard to setup the digital valve
controller for operation in an SIS solution. The Setup
Wizard automatically sets up the instrument using
specified actuator information. To access the Setup
Wizard from the Online Menu select Configure,
Guided Setup, and Setup Wizard.
1. When prompted by the Setup Wizard, enter the
pressure units (psi, bar, kPa, or kg/cm
2
).
2. Enter the maximum instrument supply pressure.
After entering the maximum instrument supply
pressure, the Setup Wizard prompts you for actuator
information.
3. Enter the partial stroke test start point.
4. Indicate if the DVC6000 SIS is connected to an
LCP100.
5. Enter the manufacturer of the actuator on which
the instrument is mounted. If the actuator
manufacturer is not listed, select Other.
6. Enter the actuator model or type. If the actuator
model is not listed, select Other.
7. Enter the actuator size.
8. Enter the Relay Type.
9. Select whether the valve is open or closed under
the zero power condition, if prompted.
Note
When completing steps 3 through 9,
refer to table 3-1 for possible
configurations for a digital valve
controller operated by a 4-20 mA input
current (point-to-point mode), and
table 3-2 for possible configurations
for a digital valve controller operated
by a 0-24 VDC power supply
(multi-drop mode).
WARNING
If you answer YES to the prompt for
permission to move the valve when
the Field Communicator is
determining the travel sensor motion,
the instrument will move the valve
through its full travel range. To avoid
personal injury and property damage
caused by the release of pressure or
process fluid, provide some
temporary means of control for the
process.
10. Indicate if a volume booster or quick release is
present.
3