Instruction Manual

DVC6000 SIS
September 2013
2-38
GE26881-B, Sheet 1
E1083-1
NOTE:
THE LOGIC SOLVER MINIMUM OUTPUT MUST BE AT
LEAST 8 mA. THE LCP100, WHEN POWERED BY THE LOOP,
CONSUMES APPROXIMATELY 4 mA.
SWITCH
TO LOOP
POSITION
8-20 mA
)
(USER SUPPLIED)
AUX )
LOOP )
LOOP *
CASE GROUND
DVC6000 SIS TERMINAL BOX
SHIELD NOT CONNECTED TO LCP100
LCP100
*
LOGIC SOLVER
OUTPUT
1
1
POINT-TO-POINT MODE
NOTE:
THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES
APPROXIMATELY 4 mA.
SWITCH
TO LOOP
POSITION
24VDC
)
(USER SUPPLIED)
CASE GROUND
DVC6000 SIS TERMINAL BOX
SHIELD NOT CONNECTED TO LCP100
LCP100
*
LOGIC SOLVER
OUTPUT
1
1
MULTI-DROP MODE
AUX )
LOOP )
LOOP *
THE DVC6000 SIS MUST BE
IN POINT-TO-POINT MODE
THE DVC6000 SIS MUST BE
IN MULTI-DROP MODE
LC340 LINE
CONDITIONER
SYS /)
FLD /)
LOOP
LOOP
E1384
Figure 2-33. Wiring for Loop-Powered Configuration; Logic Solver Wired to the FIELDVUE DVC6000 SIS then the Fisher LCP100
2