Instruction Manual
Installation
September 2013
2-37
NOTE:
THE LOGIC SOLVER MINIMUM
OUTPUT MUST BE AT LEAST 8 mA. THE
LCP100, WHEN POWERED BY THE LOOP,
CONSUMES APPROXIMATELY 4 mA.
AUX )
LOOP )
LOOP *
SWITCH TO
LOOP POSITION
CASE GROUND
SHIELD NOT CONNECTED TO LCP100
DVC6000 SIS TERMINAL BOX
LCP100
)
*
LOGIC SOLVER
OUTPUT
1
1
(USER SUPPLIED)
THE DVC6000 SIS MUST BE
IN POINT-TO-POINT MODE
LOOP
GE26881-B, Sheet 2
E1084-1
8-20 mA
NOTE:
THE LCP100, WHEN POWERED BY THE
LOOP, CONSUMES APPROXIMATELY 4 mA.
AUX )
LOOP )
LOOP *
SWITCH TO
LOOP POSITION
CASE GROUND
SHIELD NOT CONNECTED TO LCP100
DVC6000 SIS TERMINAL BOX
LCP100
24VDC
)
*
LOGIC SOLVER
OUTPUT
1
1
(USER SUPPLIED)
SYS − /)
FLD − /)
THE DVC6000 SIS MUST BE
IN MULTI-DROP MODE
POINT-TO-POINT MODE
MULTI-DROP MODE
LC340 LINE
CONDITIONER
LOOP
E1375-1
Figure 2-32. Wiring for Loop-Powered Configuration; Logic Solver Wired to the Fisher LCP100 then the FIELDVUE DVC6000 SIS
2