Instruction Manual
DVC6000 SIS
September 2013
2-34
NOTES:
1/4-18 NPT X 3/8 OD TUBING
ELECTRICAL WIRING
LOGIC SOLVER
LC340 LINE
CONDITIONER
DVC6000 SIS DIGITAL
VALVE CONTROLLER
SINGLE-ACTING SPRING AND DIAPHRAGM ACTUATOR
OR PISTON ACTUATOR WITH SPRING RETURN
(NORMALLY VALVE IS
FULLY OPEN WITH
WITH VOLTAGE TO
DIGITAL VALVE CONTROLLER)
PISTON ACTUATOR
VALVE DISC
FAILS CLOCKWISE
ON LOSS OF AIR
24VDC
PRINTED WIRING BOARD
DIP SWITCH SET FOR
MULTI-DROP (UP POSITION)
E1043
A
B
SUPPLY
Figure 2-30. Example of FIELDVUE DVC6000 SIS Digital Valve Controller Installed in a 2-Wire SIS System (without a Solenoid Valve)
Make connections to the line conditioner as follows:
CAUTION
Do not overtighten the wiring
connection terminals or subject them
to heavy lateral (pushing) loads. This
could damage the line conditioner.
1. Be sure the digital valve controller DIP switch is set
for multi-drop operation.
2. Connect the digital valve controller LOOP +
terminal to the line conditioner FLD + terminal.
3. Connect the digital valve controller LOOP −
terminal to the line conditioner FLD − terminal.
4. Connect the solenoid valve field terminals to the
line conditioner FLD + and − terminals.
5. Connect the logic solver output to the line
conditioner SYS + and − terminals.
Note
Using the digital valve controller in a
2-wire system (multi-drop operation)
with an ASCO low-power solenoid
valve EF8316G303, EF8316G304,
EFX8553G305 103594 or EFX8551G305
103594 (or an equivalent low-power
solenoid valve) requires a line
conditioner. Using a low-power piloted
solenoid valve requires a separate air
supply.
When using an EF8316G303 or
EF8316G304 ensure that the solenoid
valve’s “selection gasket” is in the
“External Position”. The use of
external piloting requires the pilot
pressure to be at least 15 psig higher
than the main line pressure.
(continued on next page)
2