Instruction Manual

Installation
September 2013
2-25
FEEDBACK CONNECTIONS TERMINAL BOX
FEEDBACK UNIT
TO FEEDBACK UNIT TERMINAL 3
TO FEEDBACK UNIT TERMINAL 2
TO FEEDBACK UNIT TERMINAL 1
GROUND
SCREW
TERMINAL 1
TERMINAL 3
TERMINAL 2
W8478-1
W8475-SIS
W8477
W8476
BASE UNIT FEEDBACK UNIT
FEEDBACK CONNECTIONS
TERMINAL BOX
Figure 2-21. Terminal Details for Connecting Base Unit and Feedback Units of Remote-Mounted Digital Valve Controllers
Using the DVC6015, DVC6025 & DVC6035
Feedback Unit as a Remote Travel Sensor
1. On the feedback unit, remove the housing cap.
2. On the base unit, remove the feedback
connections terminal box cap (see figure 2-16).
3. If necessary, install conduit between the feedback
unit and the base unit following applicable local and
national electrical codes. Route the 3-conductor
shielded cable between the two units (refer to
figure 2-21).
4. Connect one wire of the 3-conductor shielded cable
between terminal 1 on the feedback unit and terminal
1 on the base unit.
5. Connect the second wire of the 3-conductor
shielded cable between terminal 2 on the feedback
unit and terminal 2 on the base unit.
6. Connect the third wire of the 3-conductor shielded
cable between terminal 3 on the feedback unit and
terminal 3 on the base unit.
7. Connect the cable shield or drain wire to the
ground screw in the feedback connections terminal
box of the base unit.
Note
Do not connect the shield or drain wire
to any terminal on the feedback unit,
to the earth ground, or any other
alternative ground.
8. Replace and hand tighten all covers.
2