Instruction Manual
DVC6000 SIS
September 2013
2-24
SAFETY GROUND
LOOP−
LOOP+
EARTH GROUND
TALK+
TALK−
39B3399-B Sheet 2
Figure 2-20. FIELDVUE DVC6000 SIS Digital Valve Controller
Terminal Box
Remote Travel Sensor Connections
The DVC6005 SIS base unit is designed to receive
travel information via a remote sensor. The remote
sensor can be any of the following:
Emerson Process Management supplied
DVC6015, DVC6025 or DVC6035 feedback unit,
An under-traveled 10 kOhm potentiometer used
in conjunction with onboard 30 kOhm resistor, or
A potentiometer used in conjunction with two
fixed resistors (potentiometer travel is the same as
actuator travel).
WARNING
Personal injury or property damage,
caused by wiring failure, can result if
the feedback wiring connecting the
base unit with the remote feedback
unit shares a conduit with any other
power or signal wiring.
Do not place feedback wiring in the
same conduit as other power or
signal wiring.
Note
3-conductor shielded cable, 22 AWG
minimum wire size, is required for
connection between base unit and
feedback unit. Pneumatic tubing
between base unit output connection
and actuator has been tested to 15
meters (50 feet) maximum without
performance degradation.
2