Instruction Manual

Installation
September 2013
2-21
24/48 VDC
110/220 VAC, etc.
Port A
CONTROL SIGNAL
(420 mA, 020 mA,
024 VDC)
Port B
SUPPLY PRESSURE
MONITORING LINE
CONTROL LINE
DVC6000 SIS DIGITAL VALVE
CONTROLLER WITH RELAY C
SPRING RETURN ACTUATOR
E1048
Figure 2-19. Pneumatic Hookup for Solenoid Testing
Special Construction to Support Logic
Solver Initiated Solenoid Valve Health
Monitoring
In single-acting actuator applications with a solenoid
valve installed, the DVC6000 SIS can be configured to
monitor the health of the solenoid valve test, which is
initiated by the Logic Solver. This is accomplished by
connecting the unused output port B from the
DVC6000 SIS to the pneumatic monitoring line
between the solenoid valve and the actuator, as
shown in figure 2-19. When single-acting, direct relay
C is installed, the “unused” output port is port B. When
single-acting, reverse relay B is used, the unused port
is port A.
Note
This application is called “special
application” in the Setup Wizard relay
selection.
This configuration is not possible with
a double-acting actuator or when
using relay A in single-acting mode.
2