Instruction Manual
DVC6000 SIS
September 2013
1-10
Table 1-6. Hazardous Area Classifications—ATEX
Certificate Type Certification Obtained Entity Rating Temperature Code
Enclosure
Rating
ATEX
DVC60x0
DVC60x0S
(x = 1,2,3)
II 1 G D
Intrinsically Safe
Gas
Ex ia IIC T5/T6 Ga
Dust
Ex ia IIIC T85C (Ta ≤ +73C), T92C
(Ta ≤ +80C) Da
Per drawing GE60771
Natural Gas Approved
Ui = 30 VDC
Ii = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
T5(Tamb ≤ 80C)
T6(Tamb ≤ 75C)
IP66
Single Seal Device
II 2 G
Flameproof
Gas
Ex d IIC T5/T6 Gb
Natural Gas Approved
− − −
T5(Tamb ≤ 85C)
T6(Tamb ≤ 80C)
IP66
Single Seal Device
II 3 G
Type n
Gas
Ex nC IIC T5/T6 Gc
Natural Gas Approved
− − −
T5(Tamb ≤ 80C)
T6(Tamb ≤ 75C)
IP66
Single Seal Device
DVC6005
II 1 G D
Intrinsically Safe
Gas
Ex ia IIC T5/T6 Ga
Dust
Ex ia IIIC T85C (Ta ≤ +76C), T89C
Ta ≤ +80C) Da
Per drawing GE60771
Natural Gas Approved
Ui = 30 VDC
Ii = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
Uo = 9.6 VDC
Io = 3.5 mA
Co = 3.6 uF
Lo = 100 mH
Po = 8.4 mW
T5(Tamb ≤ 80C)
T6(Tamb ≤ 75C)
IP66
Single Seal Device
II 2 G
Flameproof
Gas
Ex d IIC T5/T6 Gb
Natural Gas Approved
− − −
T5(Tamb ≤ 85C)
T6(Tamb ≤ 80C)
IP66
Single Seal Device
II 3 G
Type n
Gas
Ex nC IIC T5/T6 Gc
Natural Gas Approved
− − −
T5(Tamb ≤ 80C)
T6(Tamb ≤ 75C)
IP66
Single Seal Device
DVC60x5
(x = 1,2,3)
II 1 G D
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6 Ga
Dust
Ex ia IIIC T85C (Tamb ≤ +64C) T100C
(Tamb ≤ +79C), T135C (Tamb ≤ +114C)
T146C (Tamb ≤ +125C) Da
Per drawing GE60771
Ui = 30 VDC
Ii = 100 mA
Ci = 0 uF
Li = 0 mH
Pi = 160 mW
T4(Tamb ≤ 125C)
T5(Tamb ≤ 95C)
T6(Tamb ≤ 80C)
IP66
II 2 G
Flameproof
Gas
Ex d IIC T4/T5/T6 Gb
− − −
T4(Tamb ≤ 125C)
T5(Tamb ≤ 95C)
T6(Tamb ≤ 80C)
IP66
II 3 G
Type n
Gas
Ex nA IIC T4/T5/T6 Gc
− − −
T4(Tamb ≤ 125C)
T5(Tamb ≤ 95C)
T6(Tamb ≤ 80C)
IP66
1