Instruction Manual

DVC6000 SIS
September 2013
1-6
Table 1-2. Specifications (continued)
Connections
Supply Pressure: 1/4 NPT internal and integral
pad for mounting 67CFR regulator
Output Pressure: 1/4 NPT internal
Tubing: 3/8-inch, recommended
Vent: 3/8 NPT internal
Electrical: 1/2 NPT internal conduit connection,
M20 adapter optional
Stem/Shaft Travel
Linear Actuators with rated travel between
6.35 mm (0.25 inch) and 606 mm (23.375 inches)
Rotary Actuators with rated travel between 50
degrees and 180 degrees.
Mounting
Designed for direct actuator mounting or remote
pipestand or wall mounting. Mounting the
instrument vertically, with the vent at the bottom of
the assembly, or horizontally, with the vent pointing
down, is recommended to allow drainage of
moisture that may be introduced via the instrument
air supply.
Weight
Valve-Mounted Instruments
Aluminum: 3.5 kg (7.7 lbs)
Stainless Steel: 7.7 kg (17 lbs)
Remote-Mounted Instruments
DVC6005 SIS Base Unit: 4.1 kg (9 lbs)
DVC6015 Feedback Unit: 1.3 kg (2.9 lbs)
DVC6025 Feedback Unit: 1.4 kg (3.1 lbs)
DVC6035 Feedback Unit: 0.9 kg (2.0 lbs)
Construction Materials
Housing, module base and terminal box:
A03600 low copper aluminum alloy (standard)
CF8M (cast 316 stainless steel) (optional for
valve-mounted instruments only)
Cover: Thermoplastic polyester
Elastomers
Standard: Nitrile
Optional: Fluorosilicone
Options
Supply and output pressure gauges or Tire
valves, Integral mounted filter regulator,
Stainless steel housing, module base, and
terminal box, Extreme Temperature, Beacon
Indicator, LCP100 local control panel Natural
Gas Certified, Single Seal Device, Feedback
Assembly PTFE Sleeve Protective Kit for aluminum
units in saltwater or particulate environments
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 3 paragraph
3 of the Pressure Equipment Directive (PED) 97 /
23 / EC. It was designed and manufactured in
accordance with Sound Engineering Practice (SEP)
and cannot bear the CE marking related to PED
compliance.
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 Process Instrument Terminology.
1. 3-conductor shielded cable, 22 AWG minimum wire size, is required for connection between base unit and feedback unit. Pneumatic tubing between base unit output connection and actuator
has been tested to 91 meters (300 feet). At 15 meters (50 feet) there was no performance degradation. At 91 meters there was minimal pneumatic lag.
2. The pressure/temperature limits in this document and any applicable code or standard should not be exceeded.
3. Values at 1.4 bar (20 psig) based on a single-acting direct relay; values at 5.5 bar (80 psig) based on double-acting relay.
4. Normal m
3
/hour Normal cubic meters per hour at 0C and 1.01325 bar, absolute. Scfh Standard cubic feet per hour at 60F and 14.7 psia
5. Typical value. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also, not applicable to DVC6020 SIS digital valve controllers in long-stroke
applications.
6. Temperature limits vary based on hazardous area approval
1