Instruction Manual

Introduction and Specifications
September 2013
1-5
Table 1-2. Specifications (continued)
Electromagnetic Interference (EMI)
Meets EN 61326-1 (First Edition)
Immunity—Industrial locations per Table 2 of
the EN 61326-1 standard. Performance is
shown in table 1-3 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Lightning and Surge Protection—The degree of
immunity to lightning is specified as Surge immunity
in table 1-3. For additional surge protection
commercially available transient protection devices
can be used.
Vibration Testing Method
Tested per ISA-S75.13 Section 5.3.5. A resonant
frequency search is performed on all three axes.
The instrument is subjected to the ISA specified 1/2
hour endurance test at each major resonance, plus
an additional two million cycles.
Input Impedance (Point-to-Point only)
The input impedance of the DVC6000 SIS active
electronic circuit is not purely resistive. For
comparison to resistive load specifications, an
equivalent impedance of 550 ohms may be used.
This value corresponds to 11 V @ 20 mA.
Operating Ambient Temperature Limits
(2,6)
40 to 85C (40 to 185F) for most approved
valve-mounted instruments
60 to 125C (76 to 257F) for remote-mounted
feedback unit
52 to 85C (62 to 185F) for valve-mounted
instruments utilizing the Extreme Temperature
option (fluorosilicone elastomers)
Humidity Limits
0 to 100% condensing relative humidity with
minimal zero or span shifts
Electrical Classification
Hazardous Area
CSA—Intrinsically Safe, Explosion-proof,
Division 2, Dust Ignition-proof
FM—Intrinsically Safe, Explosion-proof,
Non-incendive, Dust Ignition-proof
ATEX—Intrinsically Safe, Flameproof, Type n
IECEx—Intrinsically Safe, Flameproof, Type n
Electrical Housing
CSA—Type 4, IP66
FM—Type 4, IP66
ATEX—IP66
IECEx—IP66
Refer to tables 1-4, 1-5, 1-6 and 1-7, Hazardous
Area Classifications and Special Instructions for
“Safe Use” and Installation in Hazardous Locations
in Section 2, and Appendix B for specific approval
information.
Pollution Degree 2, Overvoltage Category III per
ANSI/ISA-82.02.01 (IEC 61010-1 Mod).
Auxiliary Terminal Contact: Nominal Electrical
Rating 5 V, <1 mA; It is recommended that the
switch be sealed or have gold plated contacts to
avoid corrosion.
For proper operation of the auxiliary input terminal
capacitance should not exceed 18000pF.
Other Classifications/Certifications
Gas Certified, Single Seal Device CSA, FM,
ATEX, and IECEx
FSETAN—Federal Service of Technological,
Ecological and Nuclear Inspectorate (Russia)
GOST-R—Russian GOST-R
INMETRO— National Institute of Metrology,
Quality, and Technology (Brazil)
KGS—Korea Gas Safety Corporation (South Korea)
KISCO—Korea Industrial Safety Corporation (South
Korea)
NEPSI— National Supervision and Inspection
Centre for Explosion Protection and Safety of
Instrumentation (China)
PESO CCOE— Petroleum and Explosives Safety
Organisation Chief Controller of Explosives (India)
TIIS— Technology Institution of Industrial Safety
(Japan)
Contact your Emerson Process Management sales
office for classification/certification specific
information
IEC 61010 Compliance Requirements
(Valve-Mounted Instruments only)
Power Source: The loop current must be derived
from a Separated Extra-Low Voltage (SELV) power
source.
Environmental Conditions: Installation Category I
continued
1