Instruction Manual
DVC6000 SIS
September 2013
5-12
PST Calibration (1-3-5)
Access PST Calibration by selecting PST Calibration
from the Calibrate menu. Follow the prompts on the
Field Communicator display to complete the PST
calibration.
This procedure permits you to run the Partial Stroke
Calibration, which enables the Partial Stroke Test. It
establishes values for Partial Stroke Pressure Limit,
Pressure Set Point and Pressure Saturation Time for
End Point Pressure Control, Travel Deviation Alert
Point and Travel Deviation Time. The Partial Stroke
Calibration also sets default values for max travel
movement, test speed, and test pause time.
Note
You must take the instrument out of
service before running Partial Stroke
Calibration.
Ensure that the instrument is put back
in service after the completing the
calibration procedure.
5