Instruction Manual

Instruction Manual Supplement
D103320X012
DVC6000 SIS
January 2011
4
8. If there is already Partial Stroke Test data in the DVC6000 SIS, you will see the message shown in figure 7. Select OK
and go to step 9 to continue running the Partial Stroke test using the 375 Field Communicator. Select ABORT if you
want to extract the existing data using ValveLinkā„¢ Software.
Figure 7. Data not Extracted by ValveLink Software
DVC6000: SIS
There is diagnostic data in the instrument
that has not been extracted by ValveLink
.
ABORT OK
9. Select OK to confirm that you want the current Partial Stroke Test to overwrite the existing data (see figure 8) and
go to step 10. Select ABORT if you want to extract the existing data using ValveLink Software.
Figure 8. Partial Stroke Test will Overwrite Data
DVC6000: SIS
ABORT OK
Partial Stroke Test will overwrite this data.