5. Enter the maximum travel movement (figure 4) desired and select ENTER.
Figure 4. Enter Max Tvl Movement
DVC6000: SIS
Max Tvl Movement 10.0%
ABORT
ENTER
10.0
HELP
DEL
6. Choose the desired test speed for the Partial Stroke Test, as shown in figure 5, and select ENTER
Figure 5. Select the PST Test Speed
DVC6000: SIS
Test Speed (1.0 %/sec)
ABORT
ENTER
0.5 %/sec
0.25 %/sec
0.12 %/sec
0.06 %/sec
1.0 %/sec
7. Choose the desired test pause time, as shown in figure 6, and select ENTER.
Figure 6. Select the PST Pause Time
DVC6000: SIS
ABORT
ENTER
Pst Pause Time (5 sec)
5 sec
10 sec
15 sec
20 sec
30 sec