Configuring Push Button Partial Stroke Test using ValveLink⢠Software
After the successful completion of Setup Wizard select Instrument Setup > Detailed Setup and find the Initial Setup
tab. Find the Aux Terminal Mode parameter and set it to Push Button Partial Stroke Test.
Running a Partial Stroke Test via Pushbutton
Press the pushbutton for more than 3 seconds but less than 10 seconds to short the auxiliary terminals. The partial
stroke test will initiate. Once it is complete, the Diagnostic Data Available Alert will appear and a Partial Stroke Test
Signature can be viewed using ValveLink software.
Canceling a Partial Stroke Test via Pushbutton
After the partial stroke test has begun, press the pushbutton briefly to short the auxiliary terminals. This will cancel the
partial stroke test. ValveLink software will indicate that the partial stroke test was aborted by the user.