Use ValveLink software to communicate with the DVC6000 SIS. Select Status from the Diagnostics menu. Start
monitoring the status of the DVC6000 SIS and check for its control mode. If the operational mode on the nameplate is
PT-PT the control mode should be Analog, as shown in figure 3. If the operational mode on the nameplate is MULTI the
control mode should be Digital, as shown in figure 4. If the control mode does not match the nameplate, follow the
procedure to change the switch position on the PWB according to the DVC6000 SIS Instruction Manual. Refer to page
7-6, table 7‐2 of the instruction manual. When finished checking the control mode click on End Monitoring.
Figure 2. Select Status
Figure 3. Point to Point Control Mode
DIP SWITCH SET TO PT‐PT
END MONITORING