Step 7: Protection
If this is the final set up / configuration before the DVC6000 SIS is put into service Protection should be set for
“Configuration and Calibration” to protect for any inadvertent acts as per the appropriate DVC6000 SIS Safety Manual.
When protection is enabled for “Calibration and Configuration” calibration is prohibited and protected setup
parameters cannot be changed. Refer to table 4‐3 of the DVC6000 SIS Instruction Manual for conditions for modifying
DVC6000 SIS parameters.
If company guidelines do not permit protection through use of a jumper skip step 7.
To enable protection, select Change Protection from the Instrument Setup menu. Follow the prompts to enable
protection.
Figure 35. Enable Protection