LCP100 Local Control Panel
November 2013
8
Figure 5. Wiring for Loop‐Powered Configuration; Logic Solver Wired to the Fisher LCP100 then the FIELDVUE
DVC6200 SIS ; Explosion-proof Applications
NOTE:
1 THE LOGIC SOLVER MINIMUM OUTPUT
MUST BE AT LEAST 8 mA. THE LCP100,
WHEN POWERED BY THE LOOP, CONSUMES
APPROXIMATELY 4 mA.
AUX +
LOOP +
LOOP *
SWITCH TO
LOOP POSITION
CASE GROUND
SHIELD NOT CONNECTED
TO LCP100
DVC6200 SIS TERMINAL BOX
LCP100
LOGIC SOLVER
OUTPUT
1
(USER SUPPLIED)
THE DVC6200 SIS MUST BE
IN POINT‐TO‐POINT MODE
LOOP
8‐20 mA
NOTE:
1 THE LCP100, WHEN POWERED BY THE LOOP,
CONSUMES APPROXIMATELY 4 mA.
AUX +
LOOP +
LOOP *
SWITCH TO
LOOP POSITION
CASE GROUND
SHIELD NOT CONNECTED TO LCP100
DVC6200 SIS TERMINAL BOX
LCP100
24VDC
LOGIC SOLVER
OUTPUT
1
(USER SUPPLIED)
SYS  - /)
FLD  - /)
THE DVC6200 SIS MUST
BE IN MULTI‐DROP MODE
POINT‐TO‐POINT MODE
MULTI‐DROP MODE
LC340 LINE
CONDITIONER
LOOP
E1466
E1467