When connections are complete move the DIP switch to the appropriate power setting. If external 24 VDC is used to
power the LCP100, make sure the switch is on the side that says “24VDC”. If loop power is used, slide the switch to the
side that says “LOOP”.
Note
Factory default for the DIP switch power selector is 24VDC.
When installing the cover, tighten the screws evenly in a criss‐cross pattern such as the one indicated in figure 2 to
help ensure the cover is properly installed.
Figure 3. Wiring for 24 VDC External Power Configuration; Explosion-proof Applications
NOTE: DO NOT CONNECT THE LOOP + TERMINAL IN THE LCP100 TO THE LOOP + TERMINAL IN THE DVC6200 SIS.
THIS WILL CAUSE THE LCP100 TO UNNECESSARILY CONSUME 4 mA AT THE EXPENSE OF THE DVC6200 SIS.
SIMPLE METHOD FOR INSTALLING AN LCP100 TO AN EXISTING
DVC6200 SIS INSTRUMENT WHEN 24 VDC POWER IS AVAILABLE
SWITCH TO
24VDC POSITION
24 VDC
(USER SUPPLIED)
4‐20 mA
AUX +
AUX*
CASE GROUND
SHIELD NOT CONNECTED TO LCP100
24VDC +
DVC6200 SIS TERMINAL BOX
LCP100
SOURCE
24VDC *
1
1 THIS CONNECTION IS ALSO LABELED LOOP -.
LOGIC
SOLVER
OUTPUT
24VDC
(USER SUPPLIED)
E1465