Instruction Manual
Instruction Manual
D103272X012
LCP100 Local Control Panel
November 2013
4
The LCP100 can be connected to a DVC6200 SIS that is part of an intrinsically safe system provided that you follow the
instructions for the LCP100 Ex ic installation, as shown in figures 4 and 7. The overall intrinsically safe system would be
rated as an Ex ic system.
For all other approvals use zone 1 approved wiring practices.
CSA
Ex em IIC, IP66
Rated 30 VDC maximum; 100 mA maximum; temperature code rating T4, ambient temperature range -40_C to 65_C
Special Conditions of Use
1. Install in an area that has a low risk of mechanical damage.
2. Install the cover, tightening the screws evenly in a criss‐cross pattern such as the one indicated in figure 2 to help
ensure the cover is properly installed.
Figure 2. Proper Cover Installation
NOTE: TIGHTEN THE SCREWS IN A CRISS‐CROSS PATTERN TO
HELP ENSURE PROPER COVER INSTALLATION
1
2
3
4
ATEX / IECEx
ATEX: II 2G Ex e mb [ib] IIC T4 Gb
ATEX: II 3G Ex ic IIC T4 Gc
IECEX: Ex e mb [ib] IIC T4 Gb
ATEX: Ex ic IIC T4 Gc
Ta = -40_C to +65_C
IP66
Entity parameters for intrinsically safe applications: Ui = 27 VDC, Ci = 1.1 nF, and Li = 0
Standards Used for Certification
IEC 60079-0:2004
IEC 60079-0:2007
IEC 60079-7:2006
IEC 60079-11:2006
IEC 60079-18:2004
EN 60079-0:2006
EN 60079-7:2007
EN 60079-11:2007
EN 60079-18:2004