LCP100 Local Control Panel
November 2013
10
Figure 7. Wiring for Loop‐Powered Configuration; Logic Solver Wired to the FIELDVUE DVC60200 SIS then the
Fisher LCP100; Intrinsically Safe Applications
NOTE:
1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE AT LEAST 8 mA.
THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES
APPROXIMATELY 4 mA.
SWITCH TO
LOOP POSITION
8‐20 mA
(USER SUPPLIED)
AUX +
CASE GROUND
DVC6200 SIS TERMINAL BOX
SHIELD NOT
CONNECTED TO LCP100
LCP100
LOGIC SOLVER
OUTPUT
1
POINT‐TO‐POINT MODE
THE DVC6200 SIS MUST BE
IN POINT‐TO‐POINT MODE
LOOP
LOOP +
LOOP*
INTRINSICALLY
SAFE BARRIER
NON-HAZARDOUS LOCATION HAZARDOUS LOCATION