Data Sheet

DVC6200 SIS Digital Valve Controller
D103555X012
Product Bulletin
62.1:DVC6200 SIS
September 2013
7
Specifications
Available Mounting
J Sliding‐stem linear applications
J Quarter‐turn rotary applications
J Integral mounting to Fisher rotary actuators
J Integral mounting to the Fisher GX control valve and
actuator system
DVC6200 SIS digital valve controllers can also be
mounted on other actuators that comply with
IEC 60534‐6‐1, IEC 60534‐6‐2, VDI/VDE‐3845, and
NAMUR mounting standards
Communication Protocol
J HART 5 or J HART 7
Input Signal
Point‐to‐Point
Analog Input Signal: 4‐20 mA DC, nominal
Minimum Voltage Available at Instrument Terminals
must be 9.5 VDC for analog control, 10 VDC for HART
communication
Minimum Control Current: 4.0 mA
Minimum Current w/o Microprocessor Restart: 3.5 mA
Maximum Voltage: 30 VDC
Overcurrent protected
Reverse Polarity protected
Multi‐Drop
Instrument Power: 11 to 30 VDC at 10 mA
Reverse Polarity protected
Supply Pressure
(1)
Minimum Recommended: 0.3 bar (5 psig) higher than
maximum actuator requirements
Maximum: 10.0 bar (145 psig) or maximum pressure
rating of the actuator, whichever is lower
Supply Medium
Air or Natural Gas
Air: Supply pressure must be clean, dry air that meets
the requirements of ISA Standard 7.0.01.
Natural Gas: Natural Gas must be clean, dry, oil-free
and noncorrosive. H
2
S content should not exceed 20
ppm.
A maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to 5
micrometer particle size is recommended.
Output Signal
Pneumatic Output: up to full supply pressure
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action: Double, Single Direct, or Single Reverse
Electronic Output
(2)
J Integral 4‐20 mA Position Transmitter:
4‐20 mA output, isolated
Supply Voltage: 8‐30 VDC
Fault Indication: offrange high or low
Reference Accuracy: 1% of travel span
Safety Accuracy: 5% of travel span
J Integral Limit Switch: One isolated switch,
configurable throughout the calibrated travel range
or actuated from a device alert
Off State: 0 mA (nominal)
On State: up to 1 A
Supply Voltage: 30 VDC maximum
Reference Accuracy: 2% of travel span
Safety Accuracy: 5% of travel span
Steady State Air Consumption
(3)(4)
Low Bleed Relay
At 1.4 bar (20 psig) supply pressure:
0.056 normal m3/hr (2.1 scfh), average
At 5.5 bar (80 psig) supply pressure:
0.184 normal m3/hr (6.9 scfh), average
Maximum Output Capacity
(3)(4)
At 1.4 bar (20 psig) supply pressure:
10.0 normal m3/hr (375 scfh)
At 5.5 bar (80 psig) supply pressure:
29.5 normal m3/hr (1100 scfh)
Operating Ambient Temperature Limits
(1)(5)
-52 to 85_C (-62 to 185_F)
Independent Linearity
(6)
Typical Value: +/-0.50% of output span
Electromagnetic Compatibility
Meets EN 61326‐1 (First Edition)
Immunity‐Industrial locations per Table 2 of the
EN 61326‐1 standard
Emissions-Class A
ISM equipment rating: Group 1, Class A
Vibration Testing Method
Tested per ANSI/ISA S75.13.01 Section 5.3.5
Input Load Impedance
An equivalent impedance of 500 ohms may be used.
This value corresponds to 10V @ 20 mA.
‐continued‐