Data Sheet

DVC6200 SIS Digital Valve Controller
D103555X012
Product Bulletin
62.1:DVC6200 SIS
September 2013
5
Figure 5. De-Energize to Trip (DETT) FIELDVUE DVC6200 SIS; No Solenoid Valve
Options Available
n LCP100 Local Control Panel or external pushbutton
n Integral 4-20 mA position transmitter or discrete switch
Benefits
n DVC6200 SIS provides diagnostic coverage with PST
n Eliminates solenoid valve
n When powered by 4-20 mA, the DVC6200 SIS is capable of
recording the demand and reset stroke
Operation
n DVC6200 SIS will move to the safety demand state upon signal
deenergization, loss of power, or loss of pneumatic supply
LC340 mounting requires standard 35 mm DIN rail; install in marshalling or I/O cabinet, or junction box. For
additional information refer to the LC340 instruction manual (D102797X012), available at www.FIELDVUE.com
or from your Emerson Process Management sales office.
1
LOGIC SOLVER
AS
4-20 mA DETT
0-24 VDC DETT
LOGIC SOLVER
LC340
LINE CONDITIONER
AS
1
E1457
E1458