Application Examples
Figure 4. De-Energize to Trip (DETT) FIELDVUE DVC6200 SIS and DETT Solenoid Valve
Options Available
n LCP100 Local Control Panel or external pushbutton
n Integral 4-20 mA position transmitter or discrete switch
Benefits
n DVC6200 SIS provides diagnostic coverage with PST
n DVC6200 SIS used with solenoid can provide redundant safety function
n DVC6200 SIS can provide additional diagnostic coverage when optional
solenoid pulse recording is utilized
n When powered by 4-20 mA, the DVC6200 SIS is capable of recording the
demand and reset stroke
Operation
n DVC6200 SIS will move to the safety demand state upon signal
deenergization, loss of power, or loss of pneumatic supply
An LC340 line conditioner is required for 0-24 VDC DETT
LC340 mounting requires standard 35 mm DIN rail; install in marshalling or I/O cabinet, or junction box. For
additional information refer to the LC340 instruction manual (D102797X012), available at www.FIELDVUE.com
or from your Emerson Process Management sales office.
1
1
LOGIC SOLVER
OR DCS
LOGIC SOLVER
4-20 mA DETT
OR 0-24 VDC DETT
0-24 VDC DETT
AS
S
0-24 VDC DETT
LOGIC SOLVER
FISHER LC340
LINE CONDITIONER
LOW POWER
SOLENOID VALVE
AS
S
2
2
2
E1455
E1456