Instruction Manual
Instruction Manual Supplement
D103858X012
DVC6200 SIS
March 2014
9
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
Valve Stuck (PST Unsuccessful)
ValveLink
Software
SERIAL
IN OUT
MULTIPLEXER**
BPCS SIS FIELD
OUT IN
IN OUT
AI or DI*
DO
IN OUT
DO
Optional LCP100 or
External Pushbutton PST
S
Optional Position Feedback
(420 mA Analog
or 1 A Discrete Switch)
0-24 V DC
0-24 V DC + HART
HART
LC340
Options Available:
LCP100 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
Notes:
Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
Trigger diagnostics or capture of
demand/reset strokes unavailable since
power to DVC6200 SIS is interrupted during
a demand
Benefits:
SIL3 Capable digital valve controller
‐Redundant DVC6200 SIS and SOV
PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid health monitoring
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink Software or 475 Field Communicator can be used in lieu of multiplexer
Scenario 8: SIS with separate DO to DETT DVC6200 SIS and DETT SOV
Instrument
Air Supply