Instruction Manual

Instruction Manual Supplement
D103858X012
DVC6200 SIS
March 2014
9
DISPLAY ALARMS
ESDV STATUS
IN PROGRESS
Valve Stuck (PST Unsuccessful)
ValveLink
Software
SERIAL
IN OUT
MULTIPLEXER**
BPCS SIS FIELD
OUT IN
IN OUT
AI or DI*
DO
IN OUT
DO
Optional LCP100 or
External Pushbutton PST
S
Optional Position Feedback
(420 mA Analog
or 1 A Discrete Switch)
0-24 V DC
0-24 V DC + HART
HART
LC340
Options Available:
LCP100 Local Control Panel or
external pushbutton
SIL 2 Capable 420 mA position
transmitter or discrete switch
Discrete switch can be configured
for position or alert annunciation
Notes:
Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
Trigger diagnostics or capture of
demand/reset strokes unavailable since
power to DVC6200 SIS is interrupted during
a demand
Benefits:
SIL3 Capable digital valve controller
‐Redundant DVC6200 SIS and SOV
PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid health monitoring
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink Software or 475 Field Communicator can be used in lieu of multiplexer
Scenario 8: SIS with separate DO to DETT DVC6200 SIS and DETT SOV
Instrument
Air Supply