Data Sheet

LCP100 Local Control Panel
D103604X012
Product Bulletin
62.1:LCP100
November 2013
2
Specifications
Power Options (switch selectable)
J External: 24 VDC +/- 10% @ 50 mA maximum
continuous current (100 mA maximum inrush)
J Loop: 8-20 mA (LCP100 and DVC6200 SIS
combined)
Temperature Limits
(1)
-40 to 65_C (-40 to 149_F)
Maximum distance between LCP100 and
DVC6200 SIS digital valve controller
Cable length is limited by maximum cable
capacitance of 100,000 pF
(2)
. Typical 314 meters
(1030 feet) with 18 AWG shielded Audio, Control
and Instrumentation Cable
Electrical Classification
CSA— Ex em IIC T4
Suitable for Zone 1 and Zone 2 locations
ATEX— Ex e mb [ib] IIC T4 Gb
Suitable for Zone 1 and Zone 2 locations
Ex ic IIC T4 Gc
Suitable for Zone 2 locations
IECEx— Ex e mb [ib] IIC T4
Suitable for Zone 1 and Zone 2 locations
Ex ic IIC T4 Gc
Suitable for Zone 2 locations
Refer to table 1 and 2 for specific approval
information
Electrical Housing:
IP66
Electromagnetic Interference (EMI)
Meets EN 61326-1 (First Edition)
 Immunity—Industrial locations per Table 2 of
  EN 61326-1 Standard. Performance is
  shown in table 3 below.
 Emissions—Class A
  ISM equipment rating: Group 1, Class A
Connections
Conduit:
J 3/4 NPT or J M20
Wiring
14 to 26 AWG
Electrical Installation
Wire connections are polarity sensitive
Installation Orientation
Wiring entrance must be pointed down for
self-draining
Pushbuttons
Protected with lockable covers
Dimensions
253.1 mm (10 inches) long by 109.5 mm (4.3 inches)
wide by 127.8 mm (5 inches) deep. See figure 1.
Construction Materials
Housing material: filled polyester
Approximate Weight
2.2 kg (4.9 lbs)
Lights
Green: Solid when the valve is at its normal operating
position, and loop current is normal. Flashing when
the valve is not at its normal operating position, and
loop current is normal.
Red: Solid when the valve is at its Fail Safe State and
loop current is tripped. Flashing when valve is not at
its Fail Safe State and loop current is tripped.
Yellow (Ready-to-Reset): Solid when the valve is
latched in the trip position, and loop current is
normal.
Pushbuttons
Green: After an emergency demand— commands the
valve to its normal position only after control current
is restored (manual reset).
Red: Always commands the valve to its Fail Safe State
regardless of the control current.
Black: Commands the configured partial stroke test.
Can be overridden by the Close button, Open button,
or Emergency Demand.
1. The pressure/temperature limits in this document and any other applicable code or standard should not be exceeded.
2. DVC6000 SIS: Cable length is limited by maximum cable capacitance of 18000 pF.